Mount the pumpout unit, Rig the storage tank – Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB User Manual
Page 3
Table 1 — Positive Pressure System Assembly Numbers
POSITIVE PRESSURE
SYSTEM ASSEMBLY
NUMBER
PUMPOUT UNIT
ASSEMBLY NO.
REFRIGERANT
COMPRESSOR MOTOR
(V-Ph-Hz)
MAXIMUM
RLA
LRA
STORAGE
TANK
19XB04280205
19EA42-748
R-22
208-3-60
13.2
63.5
28 cu ft
19XB04280206
19EA44-748
R-22
230-3-60
11.5
57.5
28 cu ft
19XB04280207
19EA46-748
R-22
400/460-3-50/60
5.8
28.8
28 cu ft
19XB04280208
19EA47-748
R-22
575-3-60
4.6
23.0
28 cu ft
19XB04280213
19EA48-748
R-134a
208-3-60
13.2
63.5
28 cu ft
19XB04280214
19EA49-748
R-134a
230-3-60
11.5
57.5
28 cu ft
19XB04280215
19EA51-748
R-134a
400/460-3-50/60
5.8
28.8
28 cu ft
19XB04280216
19EA52-748
R-134a
575-3-60
4.6
23.0
28 cu ft
19XB04280601
19EA42-748
R-22
208-3-60
13.2
63.5
None
19XB04280602
19EA44-748
R-22
230-3-60
11.5
57.5
None
19XB04280603
19EA46-748
R-22
400/460-3-50/60
5.8
28.8
None
19XB04280604
19EA47-748
R-22
575-3-60
4.6
23.0
None
19XB04280605
19EA48-658
R-134a
208-3-60
13.2
63.5
None
19XB04280606
19EA49-658
R-134a
230-3-60
11.5
57.5
None
19XB04280607
19EA51-658
R-134a
400/460-3-50/60
5.8
28.8
None
19XB04280608
19EA52-658
R-134a
575-3-60
4.6
23.0
None
19XB04520205
19EA42-748
R-22
208-3-60
13.2
63.5
52 cu ft
19XB04520206
19EA44-748
R-22
230-3-60
11.5
57.5
52 cu ft
19XB04520207
19EA46-748
R-22
400/460-3-50/60
5.8
28.8
52 cu ft
19XB04520208
19EA47-748
R-22
575-3-60
4.6
23.0
52 cu ft
19XB04520213
19EA48-748
R-134a
208-3-60
13.2
63.5
52 cu ft
19XB04520214
19EA49-748
R-134a
230-3-60
11.5
57.5
52 cu ft
19XB04520215
19EA51-748
R-134a
400/460-3-50/60
5.8
28.8
52 cu ft
19XB04520216
19EA52-748
R-134a
575-3-60
4.6
23.0
52 cu ft
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
NOTES:
1. All storage vessels are 300 psig (2068 kPa) designs per the ASME
(American Society of Mechanical Engineers) Boiler Pressure
Vessel Code, Section VIII Division 1.
2. All units above are shipped with a 15 psig (103 kPa) nitrogen charge.
3. Nominal horsepower for all pumpout units is 3.0.
Mount the Pumpout Unit —
The pumpout unit, if pur-
chased separately, may be mounted directly on the chiller or
it may be floor mounted.
MOUNTING ON THE CHILLER — See instructions pro-
vided with the chiller for mounting the pumpout unit. A typi-
cal chiller mount is shown in Fig. 2.
FLOOR MOUNTING — Select a ventilated and accessible
area, free of traffic or other hazards. Remove and discard the
4 angle supports at the base of the pumpout unit and bolt the
unit to the floor through the 4
7
⁄
16
in. holes at the base of the
pumpout unit. Special isolation is unnecessary. Contact sur-
face and dimensions for the pumpout unit are given in
Fig. 3.
Rig the Storage Tank —
The complete 19XB system
can be rigged as a single assembly. See the rigging instruc-
tions on the label attached to the assembly. Also refer to the
rigging guide (Fig. 4), physical data in Tables 2 and 3, and
contact surface and dimensions for the complete system in
Fig. 5. Lift the assembly only from the 4 points indicated in
the rigging guide. Each rigging cable must be capable of
supporting the entire weight of the assembly.
Lifting the assembly from points other than those speci-
fied may result in serious damage to the assembly and
personal injury. Rigging equipment and procedures must
be adequate for assembly. See Tables 2 and 3 for weights.
NOTE: These weights are broken down into pumpout
unit and storage tank weights. For the complete assem-
bly weight, add all components together.
3