Bacnet startup menu setup, Bacnet mode, Bacnet baud rate – LAARS X-BAC BACnet Interface Module - Install and Operating Manual User Manual
Page 5: Ms/tp address, Bacnet id, X-bac, Bacnet interface module
X-BAC BACnet Interface Module Installation and Configuration Manual
5
HT#
059294-00
B
BACneT STArTuP Menu SeTuP
-------- SETTINGS ----
Season
Winter
System Target 140
o
F
BACK ▲ ▼ SELECT
-- ARE YOU SURE? --
No
Yes
BACK ▲ ▼ SAVE
--- BACNET MODE ---
Disable
Enable
BACK ▲ ▼ SAVE
- BACNET BAUDRATE -
9600
19200
38400
BACK ▲ ▼ SAVE
----MS/TP ADDRESS----
1
[ ]
BACK ▲ ▼ SAVE
---- BACNET ID ----
477000
[
]
BACK ▲ ▼ SAVE
BACneT MODe
Enable, Disable
Default: Disable
Button: MENU/
• This menu option enables or disables the BACnet MSTP capability. When enabled,
additional BACnet settings shall be available for further customizing.
--- BACNET MODE ---
Disable
Enable
BACK ▲ ▼ SAVE
BACneT BAuD rATe
9600, 19200, 38400
Default: 19200
Button: MENU/
• For the control to communicate over a BAcnet MS/TP network, it must use the same Baud
rate as the rest of the network. The control offers three Baud Rates.
• If communication was not successful, the baud rate could be the cause. Check with the
network administrator for the network baud rate. Then match it on the control.
- BACNET BAUDRATE -
9600
19200
38400
BACK ▲ ▼ SAVE
MS/TP ADDreSS
1 to 127
Default: 64
Button: MENU/
• Each device on the MS/TP network must have a unique address.
• This is the MS/TP address on a RS485 network. Its MS/TP range is 1 though 127.
• The MS/TP address must be provided by the Network Administrator.
----MS/TP ADDRESS----
1
[ ]
BACK ▲ ▼ SAVE
BACneT ID
1 to 4,000,000
Default:
Button: MENU/
• The BACnet ID is a unique 32 bit number that identifies the control within the BACnet
network. No two ID shall be the same even if dealing across networks.
• It must be provided by the BACnet Network Administrator.
---- BACNET ID ----
[
]
BACK ▲ ▼ SAVE
LeD
Yellow LED
Flashes on communication between the BACnet Interface Module and the
control.
Green LED
Flashes on communication between the BACnet Interface Module and the
BACnet network.
Red LED
Flashes steadily to indicate the BACnet Interface Module is operational.
BACnet Interface Module
MSTP
1
2
3
A GND B
PRODUCT
COMM
RS485
X-BAC