0 trb wiring instructions, Tamper relay board – Keri Systems TRB User Manual
Page 2
Tamper Relay Board
Installation Guide
Page 2 of 3
P/N: 01513-001 Rev. D
Figure 2: Tamper Switch Installation
3.0
TRB Wiring Instructions
Refer to Figure 1 on page 1 for all instructions in this Section.
Tamper Switches
•
provides the input signal for enclosure tamper events – enclosure cover forced open and/or
enclosure removed from its mounting location
•
uses normally-open switches
•
connection is made to either or both J3 and J5 (the switch connections are designed in parallel)
•
requires two-conductor, AWG 22 wire
Bypass Jumpers
•
used if a tamper switch is NOT used in one of the two switch positions (single-switch application)
•
factory default is jumpers ON (bypasses both Tamper Switches)
•
remove the corresponding jumper when a tamper switch is installed
-
remove Bypass Jumper 1 (J4) for switch position 1 (J3)
-
remove Bypass Jumper 2 (J6) for switch position 2 (J5)
Relay Contacts
•
completes the circuit for alarm annunciation
•
relay changes state as a tamper switch changes state
•
Keri does NOT provide the alarm annunciation device
•
requires two- or three-conductor, AWG 22 wire depending upon your alarm annunciation device
Unit Power
•
requires 12 VDC, can be tapped off of the controller’s power
•
requires two-conductor, AWG 22 wire
Enclosure
Wall
Tamper
Switch
Switch
Plunger
Switch
Connection
Wires
Outside of
Enclosure