Page 5: Duct lengths

background image

5

Eclipse AirHeat v1.0 - Installation Guide No. 140, 11/4/03

Figure 5–Mounting & Duct Lengths

• Provide at least 3" (76 mm) clear-

ance between burner and top, bot-
tom and sides of the duct.

• Profile plates are not required for

good burner operation, but uni-
form velocity must be maintained
for full length of burner. If velocity
is not uniform, profile plates can
be used to correct this condition.

In-Duct

Sealed

Duct Press: +0.2" to –0.5" w.c.

+0.5 to –1.2 mbar

Slot-Fired

Duct Press: 0" to –0.5" w.c.

0 to –1.2 mbar

Guidelines for All Mounting Arrangements

• Center the burner in the duct.

• Allow a minimum of 46" (1168 mm) from burner to nearest point

of possible flame impingement at an input of 1,000,000 Btu/hr.
(962 kW/m).

• On burners longer than 36" (914 mm), use a hanger or a pedes-

tal to support the blower and motor.

Duct Lengths

Min./Max. Velocity: 500 to 6000 fpm

2.54 to 30.48 m/s

1000 to 4000 fpm
5.08 to 20.32 m/s

Optimum Velocity:

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Min./Max. Velocity: 500 to 6000 fpm

2.54 to 30.48 m/s

1000 to 4000 fpm
5.08 to 20.32 m/s

Optimum Velocity:

Minimum Distance Before

Possible Flame Impingement = 46"

AH

Burner

Minimum Distance Before Transition

Rectangular Ducts: One Height or Width, Whichever is Greater

Round Ducts: One Diameter

7.5°

Maximum

Air Flow