beautypg.com

Air for combustion and ventilation – Desa Tech CSPINT User Manual

Page 6

background image

www.desatech.com

111487-01E

6

DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a

confined or unconfined space.
Space:

Includes the room in which you will

install heater plus any adjoining rooms with door-

less passageways or ventilation grills between

the rooms.
1. Determine the volume of the space (length x

width x height).

Length x Width x Height = ________cu. ft.

(volume of space)

Example:

Space size 20 ft. (length) x 16 ft.

(width) x 8 ft. (ceiling height) = 2560 cu. ft.

(volume of space)

If additional ventilation to adjoining room is sup-

plied with grills or openings, add the volume of

these rooms to the total volume of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

(volume of space) x 20 = (maximum Btu/Hr

the space can support)

Example:

2560 cu. ft. (volume of space) x 20 =

51,200 (maximum Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free heater

________ Btu/Hr

Gas water heater*

________ Btu/Hr

Gas furnace

________ Btu/Hr

Vented gas heater

________ Btu/Hr

Gas fireplace logs

________ Btu/Hr

Other gas appliances* + _______ Btu/Hr

Total

= _______ Btu/Hr

* Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the

outdoors and vents to the outdoors.

Example:

Gas water heater

________ Btu/Hr

Vent-free heater + ________ Btu/Hr

Total = ________ Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

_______ Btu/Hr (maximum the space can support)

______ Btu/Hr (actual amount of Btu/Hr used)

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

51,200 Btu/Hr (maximum the

space can support)

70,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the above example is a confined

space because the actual Btu/Hr used is more than

the maximum Btu/Hr the space can support. You

must provide additional fresh air. Your options

are as follows:
A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an

unconfined space, remove door to adjoining

room or add ventilation grills between rooms.

See Ventilation Air From Inside Building.

B. Vent room directly to the outdoors. See Ven-

tilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr heater, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support, the space is

an unconfined space. You will need no additional

fresh air ventilation.

WARNING: If the area in

which the heater may be oper-

ated is smaller than that defined

as an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54, Section

5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building
This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two perma-

nent openings: one within 12" of the ceiling and

one within 12" of the floor on the wall connecting

the two spaces (see options 1 and 2, Figure 2,

page 7). You can also remove door into adjoining

room (see option 3, Figure 2, page 7). Follow the

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

Section 5.3, Air for Combustion and Ventilation for

required size of ventilation grills or ducts.

40,000
30,000
70,000

This manual is related to the following products: