Coleman Echelon FC9V User Manual
Page 3
246786-CTG-B-0407
Unitary Products Group
3
AIR FLOW DATA
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM - WITHOUT FILTERS
FC9V060B12DH11
FC9V080B12DH11
Jumper Settings
High
Low
High
Low
COOL Tap
ADJ Tap
1329
898
1312
878
A
B
1133
774
1117
741
B
B
1226
842
1202
810
A
A
1039
708
996
683
B
A
1110
755
1084
725
A
C
915
637
892
618
C
B
930
646
898
619
B
C
719
529
700
511
D
B
856
603
827
580
C
A
657
526
642
500
D
A
762
566
746
532
C
C
612
523
596
500
D
C
FC9V080C16DH11
FC9V100C20DH11
Jumper Settings
High
Low
High
Low
COOL Tap
ADJ Tap*
1758
1183
2196
1498
A
B
1646
1106
1858
1167
B
B
1699
1140
2045
1363
A
A
1531
1033
1661
1054
B
A
1527
1047
1884
1201
A
C
1449
969
1597
1022
C
B
1368
930
1506
947
B
C
1213
832
1395
891
D
B
1309
897
1477
922
C
A
1116
762
1254
761
D
A
1170
808
1304
801
C
C
1031
703
1114
657
D
C
FC9V120D20DH11
Jumper Settings
High
Low
COOL Tap
ADJ Tap*
2342
1528
A
B
1904
1229
B
B
2140
1404
A
A
1700
1096
B
A
1918
1247
A
C
1643
1044
C
B
1522
967
B
C
1418
852
D
B
1494
945
C
A
1287
772
D
A
1337
802
C
C
1132
668
D
C
HIGH / LOW HEAT CFM - WITHOUT FILTERS
FC9V060B12DH11
FC9V080B12DH11
Jumper Settings
High
Low
High
Low
HEAT Tap
ADJ Tap*
1137
720
1386
962
A
Any
974
625
1322
892
B
Any
883
593
1250
849
C
Any
825
561
1159
768
D
Any
FC9V080C16DH11
FC9V100C20DH11
Jumper Settings
High
Low
High
Low
HEAT Tap
ADJ Tap*
1732
1173
1912
1237
A
Any
1631
1110
1688
1079
B
Any
1493
1008
1545
967
C
Any
1359
931
1422
899
D
Any
FC9V120D20DH11
Jumper Settings
High
Low
HEAT Tap
ADJ Tap*
2238
1465
A
Any
2014
1313
B
Any
1863
1211
C
Any
1686
1075
D
Any
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0”
w.c. external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic
air cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.