DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)

CHDV34NA, PA

FIREPLACE
INSTALLATION

Continued

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close manual shutoff valve (see Fig-
ure 37).

2.

Pressurize supply piping system by ei-
ther opening propane/LP supply tank
valve for propane/LP gas fireplace or
opening main gas valve located on or near
gas meter for natural gas fireplace, or
using compressed air.

3.

Check all joints from propane/LP sup-
ply tank or gas meter to manual shutoff
valve (see Figure 38 for propane/LP or
Figure 39 for natural). Apply commer-
cial leak test solution to all gas joints.
Bubbles forming show a leak. Correct
all leaks at once.

Pressure Testing Fireplace Gas
Connections

1.

Open manual shutoff valve (see Fig-
ure 37).

2.

Open propane/LP supply tank valve for
propane/LP fireplace or main gas valve
located on or near gas meter for natu-
ral gas fireplace.

3.

Make sure control knob of fireplace is
in the OFF position.

4.

Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 38 for propane/LP or Figure 39 for
natural). Apply commercial leak test so-
lution to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.

5.

Light fireplace (see Operating Fire-
place
, pages 24 through 26). Check all
other internal joints for leaks.

6.

Turn off fireplace (see To Turn Off Gas
to Appliance
, page 24).

Figure 37 - Manual Shutoff Valve

ON

POSITION

OFF

POSITION

Open

Closed

Manual
Shutoff
Valve

Figure 39 - Checking Gas Joints for Natural Gas Fireplace

Figure 38 - Checking Gas Joints for Propane/LP Gas Fireplace

Propane/LP Supply
Tank

Gas Valve

Manual
Shutoff Valve

Gas Meter

Gas Valve

Manual
Shutoff Valve