Cisco TD 92322GB User Manual
Page 33
TD 92322GB
2007-06-26/ Ver. D
Installation and Operation Manual
Integrated Message Server, IMS/IP-WiFi
30
Activate Output Action
The output is set to the initial state again.
Example 2
When the door to one of the cold-storage rooms is opened, the input “Cold-storage room
1” is closed. If the door is open longer than 2 minutes a message is sent and lamp above
the door is lit. Another message is sent after 10 minutes if the door still is open. After 30
minutes another message is sent and the siren starts to sound. When the door is closed
the siren and lamp is turned off.
Cold-storage room 1, door open
Input Trigger
When the door has been open for 2 minutes (120 seconds), the action is started. The
action should not be repeated so the “Repetition time” is not stated, and then the value in
the “Max. No. of Repetitions” field has no meaning.
Send Message Actions
Activate Output Action
The duration is not defined which means that the lamp will be lit until another action is
started.
Cold-storage room 1, door open reminder
Input Trigger
When the door has been open for 10 minutes (600 seconds), another message should be
sent.
Output
Activation Duration
Siren
Low
–
Input
Activation Activation
time (s)
Repetition
time (s)
Max. No. of
Repetitions
Cold-storage room 1 Close
120
–
100
Handset Address
Message text
Beep code
1440
Cold-storage room 1,
door is open
2
Output
Activation Duration
Lamp cold-storage 1 High
–
Input
Activation Activation
time (s)
Repetition
time (s)
Max. No. of
Repetitions
Cold-storage room 1 Close
600
–
100