Listing and Code Approvals

A. Appliance Certification

The Gas Log Hearth Kits have been tested and listed in the

U.S. in accordance with

ANSI Z21.84-2003 (Gas Log Set).

They have been listed by OMNI Test Labs for installation and

operation in the United States and Canada as described in

these Installation and Operating Instructions. All components

are UL, OMNI or CSA safety certified.
Check with your local building code agency prior to installing

this appliance to ensure compliance with local codes,

including the need for permits and follow-up inspections. In

the absence of local codes, comply with the

National Fuel

Gas Code, ANSI Z223.1-Latest Edition in the U.S. If any

assistance is required during installation, please contact

your local dealer.

B. Table 1

Improper installation, adjustment, alteration, service

or maintenance can cause injury or property damage.

Refer to the owner’s information manual provided with

this appliance. For assistance or additional information

consult a qualified installer, service agency or the gas

supplier.

WARNING

Fire Risk

Exhaust Fumes Risk

• Do NOT use this appliance as a “vent-free

heater.

The flue must be permanently open. Refer

to Table 1.

WARNING

Product

18”

24”

Inlet BTU

Nat.

67,000

68,000

Max. Inlet Pressure

IN. WC / KPa

Nat.

10.0 / .052

10 / .052

Min. Inlet Pressure IN.

WC / KPa

Nat.

.5 / .018

.5 / .018

Orifice Size

In.

Nat.

(#28)

(#26)

Minimum Fireplace

Opening Size

In. / cm

Front

8

Rear

20

26

Depth

15

15

Height

21

21

Min. Vent Opening in

Square In. / cm

9 / 251.6

48 / 09.7

These Hearth/Log Kits are for use with all CFM Factory built fireplaces.