BLOWER / MOTOR SECTION
Unit(s)
shall
be
supplied
with
a
single
AMCA
rated
centrifugal
backward
inclined
insdustrial
statically
and
dynamically
balanced
blower.
The
fan
shall
be
mounted
on
a
heavy
duty
machined
and
polished
shaft.
The
shafts
maximum
operating
speed
is
not
to
exceed
75%
of
its
first
critical
speed.
The
bearings
and
motor
shall
be
mounted
in
the
airstream.
The
T-‐frame
motor
shall
be
mounted
in
a
motor
compartment
on
a
fully
adjustable
base.
The
bearings
are
to
be
industrial
pillow
block
type
supplied
with
extended
grease
lines.
The
blower
is
to
be
driven
with
an
(adjustable)
(fixed)
1.25
s.f.
V-‐belt
drive
package
concealed
in
a
belt
guard.
Outdoor
units
shall
have
hinged
door(s)
to
provide
easy
access
to
maintain
and
inspect
motor,
belts
&
bearings.
BURNER
SECTION
Each
unit
shall
be
equipped
with
a
wide
range
fully
modulating
direct
gas-‐fired
burner
capable
of
30:1
turndown.
The
burner
shall
have
stainless
steel
combustion
baffles,
non-‐clogging
gas
ports,
spark-‐ignited
intermittent
pilot
and
flame
safeguard
system.
Burner
combustion
must
be
clean
and
odorless.
Combustion
efficiency
must
limit
the
products
of
combustion
to
a
maximum
of
5
ppm
carbon
monoxide
and
0.5
ppm
nitrogen
dioxide.
The
burner
profile
is
to
be
equipped
with
adjustable
profile
plates.
A
heat
treated
glass
observation
port
shall
provide
a
full
view
of
flame.
Hinged
access
door(s)
are
to
be
provided
to
allow
easy
maintaince
and
inspection
for
burner,
ignitor
and
flamerod.
CONTROL/MANIFOLD COMPARTMENT
Unit
control
enclosure
to
have
hinged
access.
Terminal
strip
and
all
wiring
shall
be
numbered.
The
controls
for
the
heater
shall
include;
•
blower motor starter w/ambient compensated overloads and auxiliary contact(s).
•
primary to 120v control transformer
•
6,ooo volt ignition transformer
•
control circuit breaker and service switch
•
manual reset temperature high limit
•
flamesafeguard relay w/ LED status and flamerod
•
discharge temperature control sensor
•
differential air proving safety switch
•
automatic low temperature limit (optional)
All wiring external to control enclosure shall be run in conduit. The gas manifold shall include;
•
main gas pressure regulator
•
high gas pressure regulator (optional)
•
manual shutoff & test firing valve
•
main gas automatic shutoff valve
•
auxiliary main gas automatic shutoff valve
•
modulating control system
•
pilot pressure regulator
•
pilot automatic shutoff valve
•
pilot manual shutoff valve
•
pilot needle valve
•
multiple test ports