Energenics Air Wash User Manual
Page 3

INSTALLATION DESCRIPTION
RECEIVING, ERECTION, SHEET METAL,
AND ELECTRICAL
I.
RECEIVING
A. Inspect unit(s) inside and out for damage. Report any damages immediately
to the delivering carrier. THIS IS YOUR RESPONSIBILITY AND YOU MUST FILE ALL
CLAIMS. Please be certain you receive all the items on the Bill of Lading. Please send copy of the
Receiving Report.
B. The filter is fully assembled and shipped on its own pallet with the Target
Spray Assembly and leg extensions.
C. The Reservoir Assembly and pump are shipped on one pallet.
D. The Fan is shipped units own pallet.
II. ERECTION REQUIREMENTS
A. Determine the location with reference to minimum duct work to the tumbler,
ease of access, and inspection. Minimize the requirement for the horizontal duct.
B. If Filter is located outdoors, allow for the possibility of freezing.
C. Install fan on top of Airwasher with motor toward the outlet (rear) end to
balance the entire Airwasher weight over the 4 legs (or, if optional horizontal outlet is ordered, install
fan with motor hanging down and run a thick bead of rubberized caulk along the flanges to provide a
watertight seal). Dryer ducts must have 5% slope into the filter per drawing #4005.1.
D. Raise unit onto leg extensions, level unit to within ½’ over the length of the
unit, and bolt the feet to the base constructed by others.
E. If a Lint Bag is to be attached directly to the Filter, be sure the clearance
Below is adequate for easy removal. If Lint Bag is to be downstairs from the Airwasher, connect 8’
PVC using a transition to 12’ lint outlet/drain.
III SHEET METAL REQUIREMENTS
A. Duct design is properly done by licensed professional engineers.
Energenics accepts no responsibility or liability for duct design or installation.
B. For indoor installation all exhaust ducting must be properly sealed from the inside of unit
(watertight).