SAFTRONICS/EMERSON PARAMETERS (NO ENCLOSURE)

00.03 Acceleration

Time

5.0

00.04 Deceleration

Time

10.0

00.06

Motor

Rated

current

HP

dependent

*

00.08

Motor

rated

Voltage

480

or

240

00.10

Security

Level

L3

00.16

Analog input T2

4 to 20

00.23

Speed

Display

units

Cd

00.24

Custom Defined Scaling

0.056

00.27

Power up keypad reference

LASt

00.30

Ramp

mode

select

STD.HV

00.39

Motor rated Frequency

60

00.32

Dynamic V to F select

ON

00.33

Catch a spinning motor select

1

00.41

Voltage

mode

select

FD

00.42

Low Frequency Voltage Boost

1.0

01.01

Minimum

Speed

15

01.14

Drive

Configuration

A1.A2

01.15

Preset speed selector

6

01.28

Preset speed 8

5.0

01.41

Analog Reference 2 select

on

05.09

Motor

rated

Voltage

480

06.40

Enable

Sequencer

Latching

Off

07.10

Analog

Input

Destination

18.11

14.03

PID

main

ref.

source

18.12

14.04

PID

feedback

source

18.11

14.05

PID

ref.

source

invert

on

14.06

PID feedback source invert

on

14.08

PID

Enable

on

14.09

PID

Enable

signal

10.02

14.11

PID

Integral

0.400

14.14

PID

low

limit

0.0

14.16

PID

output

Dest.

1.26


Monitor Parameters

00.81

Set Point Frequency

Should read 5.0 Hz

00.85

Output Frequency

Will vary with suction pressure

00.88

Output amps

Should not exceed motor rated current

00.94

Analog Input 1(T2)

Signal from Pressure transducer


* Motor current need to be set for proper motor thermal protection.
MT082407