Saftronics/emerson parameters (no enclosure) – Energenics Air-Flow Optimizer 2007 User Manual
Page 9

SAFTRONICS/EMERSON PARAMETERS (NO ENCLOSURE)
00.03 Acceleration
Time
5.0
00.04 Deceleration
Time
10.0
00.06
Motor
Rated
current
HP
dependent
*
00.08
Motor
rated
Voltage
480
or
240
00.10
Security
Level
L3
00.16
Analog input T2
4 to 20
00.23
Speed
Display
units
Cd
00.24
Custom Defined Scaling
0.056
00.27
Power up keypad reference
LASt
00.30
Ramp
mode
select
STD.HV
00.39
Motor rated Frequency
60
00.32
Dynamic V to F select
ON
00.33
Catch a spinning motor select
1
00.41
Voltage
mode
select
FD
00.42
Low Frequency Voltage Boost
1.0
01.01
Minimum
Speed
15
01.14
Drive
Configuration
A1.A2
01.15
Preset speed selector
6
01.28
Preset speed 8
5.0
01.41
Analog Reference 2 select
on
05.09
Motor
rated
Voltage
480
06.40
Enable
Sequencer
Latching
Off
07.10
Analog
Input
Destination
18.11
14.03
PID
main
ref.
source
18.12
14.04
PID
feedback
source
18.11
14.05
PID
ref.
source
invert
on
14.06
PID feedback source invert
on
14.08
PID
Enable
on
14.09
PID
Enable
signal
10.02
14.11
PID
Integral
0.400
14.14
PID
low
limit
0.0
14.16
PID
output
Dest.
1.26
Monitor Parameters
00.81
Set Point Frequency
Should read 5.0 Hz
00.85
Output Frequency
Will vary with suction pressure
00.88
Output amps
Should not exceed motor rated current
00.94
Analog Input 1(T2)
Signal from Pressure transducer
* Motor current need to be set for proper motor thermal protection.