4.5 Connection screen

No.

Conn.

Designation

Function / assignment

PE

-

PE

Protective earth connection

KL1

1, 2

N, L

Supply voltage, 50/60 Hz

KL2

1

NC

Floating status message contact, break for failure

KL2

2

COM

Floating status message contact, changeover contact, common connection
(2 A, max. 250 VAC, min. 10 mA, AC1)

KL2

3

NO

Floating status message contact, normally open, make for failure

KL3

1

OUT

Analogue output, 0-10 VDC, max. 3 mA, SELV,
Output of the current motor level control coefficient:
1 V corresponds to 10% level control coefficient,
10 V correspond to 100% level control coefficient.

KL3

2, 8

GND

Reference mass for control interface, SELV

KL3

3, 7

0-10 V

Use control / actual value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input, SELV

KL3

4

+10 V

Voltage output 10 VDC (+/- 3%), max. 10 mA,
Supply voltage for ext. devices (e.g. potentiometer), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25%/-10%), max. 50 mA
Supply voltage for ext. devices
(e.g. sensors), SELV

KL3

6

4-20 mA

Use control / actual value input 4-20 mA, impedance 100 Ω, only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for MODBUS, RSB

KL3

10, 12

RSA

RS485 interface for MODBUS, RSA

Item no. 53159-5-9970 · Revision 83042 · Release 2014-07-14 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com