beautypg.com

Operating instructions – ebm-papst S2E300-AP02-50 User Manual

Page 5

background image

Operating instructions

S2E300-AP02-50

Translation of the original operating instructions

3.2 Nominal data

Motor

M2E074-DF

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Type of data definition

fa

fa

Valid for approval /
standard

CE

CE

Speed / min

-1

2700

3000

Power input / W

230

350

Current draw / A

1.10

1.55

Motor capacitor / µF

8

8

Capacitor voltage / VDB

400

400

Capacitor standard

P0 (CE)

P0 (CE)

Max. back pressure / Pa

160

50

Min. ambient temperature
/ °C

-25

-25

Max. ambient
temperature
/ °C

50

40

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

30.9

26.2

30.2

Efficiency grade N

40.7

36

40

Power input P

e

/ kW

0.28

Air flow q

v

/ m³/h

2290

Pressure increase total p

sf

/ Pa

140

Speed n / min

-1

2570

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

3.5 kg

Size

300 mm

Surface of rotor

Coated in black

Material of terminal box

ABS plastic

Material of blades

Sheet steel, coated in black

Material of guard grille

Steel, coated in black plastic (RAL9005)

Number of blades

5

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 44; Depending on installation and
position as per EN 60034-5

Insulation class

"B"

Humidity class

F1-2

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

< 0.75 mA

Electrical leads

Via terminal box, integrated capacitor
connected via terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60335-1; CE

Approval

CCC; EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 11684-5-9970 · Revision 83143 · Release 2014-05-08 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com