3.2 Nominal data

Motor

M3G084-DF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

208 .. 240

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

5700

Power input / W

750

Current draw / A

3.6
@ 208 V

Min. ambient
temperature / °C

-20

Max. ambient
temperature / °C

60

Min. temp. of flow
medium / °C

0

Max. temp. of flow
medium / °C

60

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.02

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

54.3

45.2

48.2

Efficiency grade N

67.1

58

61

Power input P

ed

/ kW

0.6

Air flow q

v

/ m³/h

485

Pressure increase total p

sf

/ Pa

2219

Speed n / min

-1

5710

Data established at point of optimum efficiency

3.4 Technical features

Mass

9.2 kg

Size

200 mm

Surface of rotor

Coated in black

Material of protective
cover

Polyflam RPP 374-ND CS1 (UL 97-V0)

Material of impeller

Aluminium sheet

Housing material

Die-cast aluminium

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 20

Insulation class

"B"

Mounting position

any

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Tach output
- Over-temperature-protected
electronics / motor
- PFC, active
- Motor current limit
- Line undervoltage / phase failure
detection
- PWM control input
- Control input 0-10 V

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

With plug

Motor protection

Locked-rotor protection

Protection class

I (if protective earth is connected by
customer)

Approval

CSA C22.2 Nr.113; UL 507; CCC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

For depth of screw, see chapter 3.1 Product drawing
; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

3.7 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2 (industrial
environment)

EMC harmonics

Acc. to EN 61000-3-2/3

EMC interference
emission

Acc. to EN 61000-6-4 (industrial
environment)