Operating instructions – ebm-papst K3G190-RD45-03 User Manual
Page 5
Operating instructions
K3G190-RD45-03
Translation of the original operating instructions
3.2 Nominal data
Motor
M3G055-CF
Phase
1~
Nominal voltage / VAC
230
Nominal voltage
range / VAC
200 .. 240
Frequency / Hz
50/60
Type of data definition
ml
Speed / min
-1
4120
Power input / W
169
Current draw / A
1.35
Min. ambient temperature
/ °C
-25
Max. ambient
temperature
/ °C
60
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category
A
Efficiency category
Static
Variable speed drive
Yes
Specific ratio
*
1.01
*
Specific ratio = 1 + p
fs
/ 100 000 Pa
Actual
Request
2013
Request
2015
Overall efficiency η
es
/ %
56
39.1
43.1
Efficiency grade N
74.9
58
62
Power input P
ed
/ kW
0.16
Air flow q
v
/ m³/h
565
Pressure increase total p
sf
/ Pa
524
Speed n / min
-1
4055
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass
1.8 kg
Size
190 mm
Surface of rotor
Thick layer passivated
Material of impeller
PA plastic
Housing material
PA plastic
Number of blades
7
Direction of rotation
Clockwise, seen on rotor
Type of protection
IP 54
Insulation class
"B"
Mounting position
Any
Condensate discharge
holes
None, open rotor
Operation mode
S1
Motor bearing
Ball bearing
Technical features
- Output 10 VDC, max. 1.1 mA
- Tach output
- Motor current limit
- Soft start
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor
- Line undervoltage detection
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
<= 3.5 mA
Motor protection
Locked-rotor protection
Cable exit
Variable
Protection class
I (if protective earth is connected by
customer)
Product conforming
to standard
EN 60335-1
Approval
CCC; EAC
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.5 Mounting data
For depth of screw, see chapter 3.1 Product drawing
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+ 80 °C
Min. permissible
ambient motor temp.
(transp./storage)
- 40 °C
Item no. 51200-5-9970 · Revision 80549 · Release 2014-05-08 · Page 5 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com