beautypg.com

Crown Verity DSC Series User Manual

Page 23

background image

22

23

23

DSC

Series

4.0

Maintenance

Troubleshooting Guide

Symptom

Possible Cause

Corrective Action

Burning of gas-air mixture

inside plenum (flashback).

Rumbling noise present.

• Heater mounted at incorrect angle.

• Excessive drafts.

• Gas leaking at orifice.

• Separation of ceramic grids.

• Ceramic grids cracked.

• Mount at a 0˚- 30˚angle from horizontal.

• Relocate heater or shield from draft.

• Check with leak detector solution.

• Replace burner.

• Replace burner.

Delayed ignition.

• Electrode out of specification.

• Low gas pressure.

• Partially blocked orifice.

• Improper orifice size.

• Incorrect gas.

• See ignition system insert.

• See Section 2.0, Gas Supply.

• Clean or replace gas orifice.

• Consult distributor.

• See unit rating plate.

Low ceramic surface

temperature or excessive

rollout.

• Dirty or plugged burner ceramics.

• Partially blocked orifice.

• Low inlet gas pressure.

• High or low manifold gas pressure.

• Foreign matter in venturi tube.

• Excessive dark spots on burner.

• Gas supply piping too small.

• Incorrect gas.

• See periodic maintenance instructions.

• Remove and clean.

• See Section 2.0, Gas Supply.

• Adjust main valve regulator as specified.

• See periodic maintenance instructions.

• See periodic maintenance instructions.

• Increase inlet pressure or replace piping.

• See unit nameplate.

Control system overheating. • Heater not mounted correctly.

• Heater mounted too close to

ceiling.

• Mounting angle 0°- 30°. Level left to right.

• Observe clearance to combustibles.

Gas odor.

• Loose pipe connection.

• Check connections. Tighten as necessary.

Heater cycles repeatedly.

• Heater located in drafty area.

• Low gas pressure.

• Thermostat located in drafty area.

• Defective flame electrode or circuit

board.

• Relocate or shield from draft.

• See Section 2.0, Gas Supply.

• Relocate thermostat.

• Replace electrode and/or circuit board.

No spark; no ignition.

• Lack of 24V incoming voltage.

• Open high voltage wire.

• Improper electrode gap.

• Loose or open wire connection.

• Poor or no equipment ground.

• Unit in “safety lockout” mode.

• Defective control module.

• Check power supply.

• Isolate and check resistance, replace if

open.

• See Ignition System specifications.

• Check all wires, tighten or replace.

• Check all connections, provide positive

earth ground.

• Interrupt power source, repeat trial

for ignition.

• Replace circuit board.

Heater lights, and “locks

out” after approximately 10

seconds.

• Poor or no equipment ground.

• Polarity is reversed.

• Low gas pressure.

• Electrode not sensing.

• Heater mounted at incorrect angle.

• Defective control module.

• Check all connections, provide positive

earth ground.

• Correct wiring.

• See Section 2.0, Gas Supply.

• Relocate or replace if electrode is defective.

• Mounting angle 0˚- 30˚.

• Replace circuit board.

Spark is present. No main

gas operation. Unit “locks

out”.

• Gas valve in “OFF” position.

• Defective gas valve.

• Defective control module.

• Turn to “ON” position.

• Isolate and check for resistance, replace

if reading open.

• Replace circuit board.

Heater will not shut off.

• Defective thermostat or wiring.

• Gas valve stuck or open.

• High gas pressure.

• Replace thermostat or repair wiring.

• Replace gas valve.

• See Section 2.0, Gas Supply.

Chart 4.1

Troubleshooting Guide