Nomenclature rc820—hp 1 y 12, Selection, Ratings & specifications – Toshiba RC820 User Manual
Page 4
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
NOMENCLATURE
RC820—HP 1 Y 12
(1)
{2) (3) {4) (5)
(1) Model (Series) No. RC820
(2) Reset Mode
HP ... Manual Reset
AP,,.. Auto Reset
(3) Current Rating 1.................. 7 AT
2 ......55 AT
3 ...... 110 AT
(4) Control Volt.
Y....... 100-120/200-240 V AC
(5) Variation
— Standard Surface Mounting
2.......Rush Mounting
12 .... Remote Reset (Standard)
72.... Remote Reset
(UL Listed/CSA Certified)
SELECTION
RESET
MOUNTING
UL & CSA
MODEL NO.
MANUAL
SURFACE
YES
RC820-HPL'
;:;jY
FLUSH
NO
RC820-HPL;:]Y2
AUTO
SURFACE
YES
RC820-APL'
:;:iY
REMOTE
SURFACE
NO
RC820-HPÌ':;;iYi2
YES
RC820-HPL
::
ìy
72
RATINGS & SPECIFICATIONS
RC820-
HP1Y
AP1Y
RC820-
HP2Y
AP2Y
RC820-
HP3Y
AP3Y
Applicable Circuit
Three-phase circuit rated up to 600V AC, 50/60 Hz—Direct
(Also, applicable to high-voltage circuit by combining with high-
voltage CT)
Rated Current
Rated Ampere-turns (AT)
7AT
55AT
11 OAT
Setting Range
75—150% of rated AT
Overload Protection
Ultimate Operating
Current
105—125% of setting current
Trip Time Setting Range
3—40 sec. for starting characteristics at 600% of setting current
Operating Time
Accuracy
±20% of setting time
Single-Phase Protection
Minimum Operating
Current
85% of setting current under one-phase completely loss (When
measured on either remaining phase).
Operating Time
Less than 4 sec.
Control Power
Rating
1 0 0
—120V/200—240 V AC,
^
50/60 Hz
Allowable Volt.
Fluctuation
85%—110%
Power Consumption
Control Power Circuit
2 VA
Detecting (CT) Circuit
0.3 VA/phase at rated current
Output Contact Capacity
1 ICo^ctTArrangement
1 NO—NC (SPDT/Form C)
Contact Capacity
120V AC-5.0A (Resistive load)
120 V AC-3.0A (Inductive load, pf = 0.40)
125V DO0.2A (L/R = 7ms)
250V DC-0.1A (UR = 7ms)
NEMA B300
Weight
Approx. 1 kg (2.2 lbs.)