Step 1-mounting the unit, Step 2-system connections, Hookup steps – American Access Systems Advantage DKLP - Single Gang - 19-100sg User Manual
Page 4
Page 4 American Access Systems / Security Brands, Inc.
sTEP 1-MOUNTING THE UNIT
Page 3 tells you what tools and instruments you will need to install your unit and presents a parts check list. Make sure
to have all the tools listed. Upon opening the box, check off the items enclosed with the unit. If any items are missing
from your unit, contact American Access Systems immediately.
The 19-100sg mounts to a standard 2 x 4 electrical box. Secure the 19-100sg to the electricial box with included 6/32 x
1/2 machine screws or for added security use the included 6/32 x 1/2 snake eye machine screws. If installing outdoors
use a approved weatherproof 2 x 4 electricial box and included rubber gasket for proper seal.
sTEP 2-sYsTEM CONNECTIONs
Study the WIRING COLOR CODE chart below and then proceed to the hookup steps.
ACU HARNEss COLOR CODEs
RED
(+) POsITIVE
6-12 volts DC
BLACK
(-) NEGATIVE
Common
LATCH CONTACTs
BROWN
RELAY COMMON
ORANGE
NORMALLY OPEN
BLUE
NORMALLY CLOsED
sHUNT CONTACTs
(Used for external alarm)
GRAY
RELAY COMMON
VIOLET
NORMALLY OPEN
YELLOW
NORMALLY CLOsED
HOOKUP sTEPs
(A). Your DKLP control unit operates on 6 to 14 volts DC. Measure the voltage from the power source to make sure
it falls within these tolerances. Locate the Red and Black wire on the ACU HARNESS and with the power off connect
Red to positive (+) and Black to negative (-).
NOTE: If you are using the optional AAS-12vdc transformer, cut the end connector from the transformer cable and
discard. Using appropriate wire nuts, connect black to black and black/white to red.
(B). Connect the device to be controlled to the appropriate control leads of the ACU HARNESS (See table 1).
(C). Double Check your connections. When you are sure that everything is hooked up correctly, apply power to the
unit. A BEEP should be heard when you press a key on the keypad.