7 | maintenance – GEA Bock HG12e CO2 User Manual
Page 22

22
D
GB
F
E
96282-02.2015-DGbFEI
7| Maintenance
HGX12e / ...
20-4 S CO
2
30-4 S CO
2
40-4 S CO
2
50-4 S CO
2
60-4 S CO
2
75-4 S CO
2
Designation
Item No.
Item No.
Item No.
Item No.
Item No.
Item No.
Set of gaskets
80372
Valve plate kit
80721
80708
80369
Set piston/
connecting rod
81065
81070
81067
81070
81071
81072
Set connecting rod
81033
80724
81033
80724
Only use genuine GEA Bock spare parts!
7.3 Recommended spare parts
7.2 Work to be carried out
7.1 Preparation
In order to guarantee optimum operational reliability and service life of the compressor,
we recommend
carrying out servicing and inspection work at regular intervals:
Oil change:
-
not mandatory for factory-produced series systems.
-
for field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.
Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliary devices such as oil sump heater, pressure switch.
WARNING
Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch lock.
7.5 Extract from the lubricants table
For operation with CO
2
the GEA Bock oil C 85 E is necessary!
Available accessories can be found on the Internet at www.gea.com
7.4 Accessories