3 | areas of application, R744 – GEA Bock HG22Р CO2 User Manual
Page 8

8
 D
 GB
 F
 E
96019-02.2015-DGbFEI
3| Areas of application
ATTENTION! Compressor operation is possible within the operating limits
shown	 in	 the	 diagrams.	 Please	 note	 the	 significance 
of the shaded areas. Thresholds should not be selected as design 
or continuous operation points.
- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature 140 °C
- Max. permissible switching frequency 8x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with frequency converter:
-
The maximum current and power consumption must not be
exceeded.	In	the	case	of	operation	above	the	mains	frequency,	
the application limit can therefore be limited.
The compressors are filled at the factory with the following oil type:
GEA Bock C 85 E (only this oil may be used)
 3.1 Refrigerants
• 
CO
2
: R744
3.2 Oil charge
3.3 Limits of application
Evaporation temperature (°C)
Condensing temperature (°C)
Suction gas superheat (K)
Suction gas temperature (°C)
Fig. 5
Max. permissible operating
pressure (LP/HP)
1)
: 40/55 bar
1)
LP = Low pressure
HP = High pressure
R744
Unlimited 
application range
The oil level must be in the 
visible part of the sight 
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
ATTENTION!
max.
min.
0,7 Ltr.
oil level
Fig. 4
~
~