5 | electrical connection – GEA Bock HА34P User Manual
Page 17
D
GB
F
E
I
Ru
17
09620-11.2014-DGbFEIRu
5| Electrical connection
The compressor and the trigger unit MP10 are operational when the H3 LED (green) lights.
5.7 Function test of the trigger unit MP 10
Pos
Procedure
LED H1 LED H2 LED H3
red
red
green
1 • Interrupt power supply (L1 or S1)
OFF
OFF
OFF
•
Release the motor temperature sensor connection (1 or 2)
•
Release the hot gas temperature sensor (if installed) (3 or 4)
2 • Restore the power supply (L1 or S1)
ON
•
Function check of motor temperature sensor: operational
ON
•
Function check of hot gas temperature sensor: operational
ON
3 •
Interrupt power supply again (L1 or S1)
OFF
OFF
OFF
•
Reconnect terminals 1 or 2 and/or 3 or 4
4 •
Restore the power supply (L1 or S1):
OFF
OFF
ON
•
MP 10 is operational again
Before start-up, troubleshooting or making changes to the control power circuit, check the functionality
of the trigger unit:
5.8 Fan motor
The fan motor for cooling the compressor is already wired in the terminal box. The power supply as
well as triggering of the compressor contactor should be made in accordance with the basic circuit
diagram (in the terminal box). The fan motor is protected by an internal temperature monitor.
Electrical data: 230 V - 1 - 50/60 Hz, 72 W - 0,53 A