CF2500/CF3500 Burner Manual

1

3

6

4

7

Standby

9

Pump
Prime

Valve-on

Delay

Trial for

Ignition

Lockout

Ignition

Carryover

Relight

Run

Motor-Off

Delay

5

2

8

Figure 12 - GeniSys 7505 Control with Optional Components

Table 5 - 7505 Status Light Explanation Table

Light
Color

On Continuously

Flashing

Red

Restricted (Hard) Lockout

Soft Lockout

Green

Flame Sensed during normal
operation (Could be stray light
during standby)

Recycle

Yellow

Control is in Pump Prime mode
or Reset button currently held
for 15+ seconds.

N/A

Table 4 - 7505 Flame Detection

Flame Detection Range

Normal = 0 to 1600 ohms

Limited = 1600 ohms to lockout

Section: Wire the Burner

Display Module:
Permanent device for
programming and diagnostics

Alarm Module:
For adding isolated low voltage
alarm contacts to the base control.
See Alarm Module Instructions for
specifi cations.

Contractor’s Tool:
Hand-held device for
programming and diagnostics

Cad Cell
Connections

Wiring
Connections

Communication Port 2

Reset Button

with Red Light

Communication Port 1

Thermostat Terminals

Green Light

Yellow Light

Optional Components:

Figure 11 - Typical Burner Sequence of Operation - 7505

Cad Cell Resistance Measurement:

If the Beckett 7505 control is equipped with the
GeniSys Display Module, part 52067U, the cad cell
resistance can be selected and read on the LCD
screen. Also, the GeniSys Contractor Tool, part
52082U, can be used for this purpose.

If these are not available, the cad cell leads can
be unplugged from the control and the resistance
measured with a meter in the conventional way.
Conduct these tests with fl ame present.