beautypg.com

Electrical – Ryobi RYI2011T User Manual

Page 12

background image

8 — English

ELECTRICAL

ELECTRIC MOTOR LOADS

It is characteristic of common electric motors in normal operation to draw up to six times their running current while start-
ing. This table may be used to estimate the watts required to start “Code G” electric motors; however, if an electric motor
fails to start or reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check
the requirements of the tool or appliance being used compared to the rated output of the generator.

Motor Size (H.P.)

Running Watts

Watts Required to Start Motor

Repulsion Induction

Capacitor

Split Phase

1/8

275

600

850

1200

1/6

275

600

850

2050

1/4

400

850

1050

2400

1/3

450

975

1350

2700

1/2

600

1300

1800

3600

3/4

850

1900

2600

1

1100

2500

3300

CAUTION:

Operating voltage and frequency requirement of all
electronic equipment should be checked prior to plugging
them into this generator. Damage may result if the
equipment is not designed to operate within a +/- 10%
voltage variation, and +/- 3 hz frequency variation from the
generator name plate ratings. To avoid damage, always
have an additional load plugged into the generator if
solid state equipment (such as a television set) is used.
A power line conditioner is recommended for some solid
state applications.

GROUND FAULT CIRCUIT INTERRUPTER

See Figure 1.
The 20 amp, 120 volt receptacles on the generator are pro-
tected by a Ground Fault Circuit Interrupter (GFCI), which
guards against the hazards of ground fault currents. An
example of ground fault current is the current that would
flow through a person who is using an appliance with faulty
insulation and, at the same time, is in contact with an elec-
trical ground such as a plumbing fixture, wet floor, or earth.
GFCI receptacles do not protect against short circuits,
overloads, or shocks.
The GFCI receptacles can be tested with the TEST and
RESET buttons.
To test:

Depress the TEST button. This should cause the Reset
button to pop out.

To restore power, depress the RESET button.

Perform this test monthly to ensure proper operation of the
GFCI. If the generator is stored outdoors, unprotected from
the weather, test the GFCI receptacle before each use.

GENERATOR CAPACITY

Make sure the generator can supply enough continuous (run-
ning) and surge (starting) watts for the items you will power
at the same time. Follow these simple steps.
1. Select the items you will power at the same time.
2. Total the continuous (running) watts of these items. This

is the amount of power the generator must produce to
keep the items running. See the wattage reference chart
at right.

3. Estimate how many surge (starting) watts you will need.

Surge wattage is the short burst of power needed to
start electric motor-driven tools or appliances such as a
circular saw or refrigerator. Because not all motors start
at the same time, total surge watts can be estimated by
adding only the item(s) with the highest additional surge
watts to the total rated watts from step 2.

Example:

Tool or Appliance

Continuous

(Running) Watts

Surge

(Starting) Watts

Refrigerator

700

1350

Portable Fan

40

120

Laptop

250

250

46 in. Flat Panel
Television

190

190

Light (75 Watts)

75

75

1255 Total

Running Watts

1350 Highest

Surge Watts

Total Continuous (Running) Watts

1255

Plus Highest Additional Surge Watts + 1350

Equals Total Generator Output Required

2605