4.5
Mounting Bolt Installation
4.5.1
HE-35 Mounting Bolt Installation
The HE-35 uses 1/2-13 x 8”’ bolts. Embed the bolts in 3500 psi reinforced concrete with a minimum
of 6”’ thickness. The threaded end of the bolt should extend 2 inches from the surface of the
floor. Use the outboard bolt holes for standard installation, the inboard bolt holes for side by side
installations, or installations near a wall or other object that would prevent access to the outboard
holes. Refer to figure 4.6 on page 20.
Figure 4.6: HE-35 Mounting Detail
20