TYPICAL SCHEMATIC WIRING DIAGRAM

MODELS : PT180 - PT240 (Dual compressor units)

LEGEND

AR

AUXILIARY RELAY

AFS

AIRFLOW SWITCH

ATB

AUXILIARY TERMINAL BLOCK

BM

BLOWER MOTOR

BMC

BLOWER MOTOR CONTACTOR

CC

COMPRESSOR CONTACTOR

CCA

AUXILIARY CONTACT

CB

CIRCUIT BREAKER

C. HTR CRANKCASE HEATER
COMP

COMPRESSOR

ECB

ELECTRONIC CONTROL BOARD

FCS

FAN CYCLING SWITCH

F

FUSE

FL

FUSE LINK

FM

FAN MOTOR (CONDENSER)

FMC

FAN MOTOR CONTACTOR

FR

FAULT RELAY

HC

HEATER CONTACTOR

HPS

HIGH PRESSURE SWITCH

HVTB

HIGH VOLTAGE TERMINAL BLOCK

HTR

HEATER

JP

JUMPER

L1

LINE 1

L2

LINE 2

L3

LINE 3

LPS

LOW PRESSURE SWITCH

LUG

LUG GROUND

NTB

NEUTRAL TERMINAL BLOCK

O/L

OVER LOAD

OHT

OVER HEAT THERMOSTAT

PDS

PUMP DOWN SOLENOID

SSPS

SOLID STATE PROTECTIVE SYSTEM

SD

SMOKE DETECTOR

TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM

UNDER VOLTAGE MONITOR
FIELD WIRING
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TERMINAL BLOCK OR TERMINATION POINT

_ _ _

+

NOTES

1. POWER SUPPLY, 380/415V-3PH-50Hz.

2. ANY WIRE REPLACEMENT SHOULD BE OF 90

0

C OR ITS

EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.

3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE

READ BROKEN LINES AS CONTINUOUS LINES.

4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR

MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPER-
ATING THE SYSTEM.

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER

TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY COOLINE.

6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVERLOAD.

7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS

SHOWN. PLEASE ALLOW 2-3 MINUTES FOR SSPS SWITCH
TO CLOSE, BEFORE STARTING THE UNIT.

8. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,

TURN OFF POWER FIRST & SET REQUIRED SETTING.

27

TO HVTB

TO HVTB

FAN MOTOR CONTROL CONNECTION

(APPLICABLE FOR FM WITH T.O.P)

B) WITH LOW AMBIENT OPTION

A) STANDARD CONNECTION

1. UVM OPTION

STANDARD OPTIONS

COMP. WITH CIRCUIT BREAKER OPTION

LOW AMBIENT OPTION

LUG

HVTB

2. SMOKE DETECTOR OPTION

C. BM ON,OFF & TRIP INDICATION OPTION

3. VOLT FREE CONTACT OPTIONS

A. UNIT ON & OFF INDICATION OPTION