1.7 INSTALLATION & TESTING

Mount the power system into the system chassis

Attach the connectors to main board by following the main board’s instructions, there

are various on pinouts / connectors in both the power system and main board, they

should match each other, otherwise the connection will cause undetectable harms.

Attach all the remaining power supply connections to the various peripherals as

needed, these connectors maybe “keyed”, so there will be only one possible way to

connect them.

Before applying power source to the system, make sure these are no loose or

incorrect connections. Please check your power system is AC source version or DC

source version, to supply the correct source.

To test the redundancy function, please supply the source to the individual power

modules. If the individual power module. Operates normally, the LED on the module

lits in GREEN, and the external warning LED also lits in GREEN. Now remove the

source from one of the individual power module, the warning buzzer in the power

system will sound, and the external warning LED which displays the status of the total

power supply system will blink/RED, the individual LED indicating the power module’s

status will not light. Meanwhile the power system will continue to backup the power

output without affecting the system’s operation.

The warming buzzer will continue sounding, the user can reset the warning buzzer by

pressing the buzzer reset switch.

Turn on the power module which is turned off for testing earlier, the sound of the

warning buzzer will disappear, the external warning LED will turn GREEN again; the

LED indicating the status of power module will light again, you may test other power

module by performing the similar procedure.