Wine-Mate SSHWC Series User Manual
Page 25
- 24 -
Low subcooling
5) High suction pressure and high head pressure
Low superheat and low subcooling
6) High suction pressure and high head pressure
High superheat
7) Low suction pressure and low head pressure
High superheat and low subcooling
8) Low suction pressure and low to normal head pressure
High superheat and high subcooling
9) Low suction pressure and low head pressure
Normal to high superheat and low subcooling
10) Low suction pressure and low head pressure
Low superheat and low subcooling
11) Low suction pressure and low to normal head pressure
High superheat and normal to high subcooling
12) Low suction pressure and normal head pressure
High superheat and normal subcooling
13) Low suction pressure and high head pressure
High superheat and high subcooling
14) Low suction pressure and high head pressure
High superheat and high subcooling
15) low to normal suction pressure and high head pressure
Normal to high superheat and high subcooling
5) Water restricted or bad water
regulator, dirty condenser
6) High cellar temperature, high
evaporator load
7) Undercharge
8)
Liquid line restricted after
receiver, solenoid valve
restricted
9) Suction line restricted
10)
Air restricted at evaporator,
evaporator iced
11) Evaporator restricted
12) Expansion valve restricted
13) Both evaporator and condenser
restricted; liquid and suction
lines connected wrong
14)
Liquid line restricted before
receiver
15) Condenser restricted
12. Condensing Unit Troubleshooting
Unit not running
1) Incorrect power supply
2) Incorrect or loose wirings
3) Failed
components
4) Low pressure control shutting down the
system
5) High pressure control shutting down the
system
1) Check for proper voltage
2) Check all wirings and connections
3) Check start relay, start capacitor,
overload protector, compressor.
4) Check for system restriction or low
refrigerant
5) Check the condenser water flow