7) If the superheat is high, check the subcooling first to know if the refrigerant
charge is sufficient. If the charge is not sufficient, add more refrigerant. If the
charge is good, then increase the evaporator suction pressure by turning the
hex nut (5/16”) clockwise. Liquid must always be charged into the hide side
when the compressor runs.
8) If the superheat is low, then decrease the evaporator suction pressure by
turning the hex nut (5/16”) counter-clockwise.
9) Both discharge and suction valves must be in the back positions before
disconnecting.
10) Close all service valves and disconnect all manifolds and hoses.
Fig. 11 Fan Speed Control Fig. 12 Expansion Valve
Fig. 13 Liquid Filter Fig. 14 Liquid Indicator
6. Pressure, Superheat and Subcooling Readings
CAUTION:
To read properly the service valves must be in the middle positions.
Complaint Possible
Causes
1) High suction pressure and low head pressure
Zero superheat and zero subcooling
2) High suction pressure and low head pressure
Low superheat and low subcooling
3) High suction pressure and high head pressure
Low superheat and high subcooling
1) Compressor may be bad
2) Expansion valve opened, too
much oil
3) Overcharge