AirControl C LED
Part Number
819703
819704
1 green LED for normal air speed
1 green LED for normal air speed
Display – Visual
1 red LED flashing for alarm
1 red LED flashing for alarm
No digital display
3 digit display with velocity reading
Units
N/A
meter per second (m/s) / FPM
Display Range
N/A
0 - 2.00 m/s / 0 - 400 FPM
Alarm Setpoint
Standard: below 0.39m/s / 78 FPM
Standard: below 0.39m/s / 78 FPM
Alarm Delay
Selectable: 15s or 30s
Selectable: 15s or 30s
Analog Output
0-10V 0-10V
Alarm Indication
1 red LED flashing & audible buzzer
1 red LED flashing & audible buzzer
Alarm Mute
Light On/Off
Night Setback On/Off
Alarm Relay
Yes, optional
Yes, optional
Battery Back Up
Yes, optional
Yes, optional
Sash High Input
Audible and orange flashing LED indicate Audible and orange flashing LED indicate
sash position switch has been tripped
sash position switch has been tripped
Mounting
Flush or surface box (option)
Flush or surface box (option)
Calibration
Factory pre-calibrated @ 0.5m/s / 100 FPM Factory pre-calibrated @ 0.5m/s / 100 FPM
Recalibration possible
Recalibration possible
Power Requirement
12 VDC (power supply included)
12 VDC (power supply included)
Orientation
Vertical / Horizontal Vertical
Front fascia: 210L x 90W x 10D mm
Front fascia: 210L x 90W x 10D mm
Monitor Dimensions (metric)
Surface box: 205L x 85W x 14D mm
Surface box: 205L x 85W x 14D mm
Front fascia: 8.27"L x 3.54"W x 0.39"D Front fascia: 8.27"L x 3.54"W x 0.39"D
Monitor Dimensions (U.S.)
Surface box: 8.07"L x 3.35"W x 0.55"D Surface box: 8.07"L x 3.35"W x 0.55"D