Table 15 — Fan Performance, 48TF008 — Horizontal Discharge Units (SI)
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(L/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
225
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1075
8.1
0.34
9.5
0.49
10.7
0.66
11.8
0.81
12.4
0.92
1125
8.4
0.39
9.7
0.53
10.9
0.71
12.0
0.89
12.5
0.98
1150
8.6
0.42
9.9
0.58
11.1
0.76
12.2
0.96
12.7
1.05
1200
8.9
0.46
10.2
0.64
11.3
0.81
12.4
1.02
12.8
1.11
1250
9.1
0.51
10.4
0.70
11.5
0.87
12.6
1.08
13.0
1.19
1300
9.4
0.56
10.7
0.75
11.7
0.93
12.7
1.14
13.2
1.25
1400
9.7
0.62
10.9
0.82
12.0
0.99
12.9
1.22
13.4
1.33
1450
10.0
0.67
11.2
0.88
12.2
1.07
13.2
1.27
13.6
1.40
1500
10.2
0.74
11.4
0.94
12.4
1.15
13.4
1.36
13.8
1.48
1550
10.5
0.80
11.7
1.02
12.7
1.23
13.6
1.44
14.0
1.56
1600
10.8
0.88
11.9
1.09
12.9
1.32
13.8
1.53
14.2
1.65
1650
11.1
0.97
12.2
1.17
13.2
1.41
14.0
1.63
14.4
1.75
1700
11.4
1.04
12.4
1.25
13.4
1.51
14.3
1.73
14.7
1.85
1750
11.7
1.12
12.7
1.35
13.7
1.61
14.5
1.85
14.9
1.97
1800
12.0
1.23
13.0
1.45
13.9
1.70
14.8
1.95
15.1
2.07
1850
12.2
1.33
13.2
1.54
14.2
1.81
15.0
2.08
15.4
2.20
1900
12.5
1.42
13.5
1.65
14.4
1.92
15.2
2.20
15.6
2.34
AIRFLOW
(L/s)
EXTERNAL STATIC PRESSURE (Pa)
250
300
350
400
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1075
12.9
1.03
13.9
1.29
15.0
1.60
15.7
1.89
1125
13.0
1.08
14.0
1.34
15.1
1.68
15.9
1.92
1150
13.1
1.13
14.1
1.38
15.2
1.69
16.0
1.96
1200
13.3
1.21
14.3
1.42
15.2
1.74
16.0
2.01
1250
13.5
1.29
14.4
1.48
15.3
1.78
16.2
2.06
1300
13.7
1.37
14.5
1.56
15.4
1.81
16.3
2.09
1400
13.9
1.44
14.7
1.66
15.5
1.84
16.4
2.19
1450
14.1
1.52
14.9
1.77
15.7
1.97
16.5
2.18
1500
14.3
1.60
15.1
1.86
15.9
2.08
16.6
2.29
1550
14.2
1.68
15.3
1.94
16.1
2.21
16.8
2.43
1600
14.8
1.77
15.5
2.04
16.3
2.31
17.0
2.55
1650
14.9
1.86
15.7
2.13
16.5
2.42
17.2
2.70
1700
15.1
1.97
15.9
2.24
16.6
2.52
17.4
2.82
1750
15.3
2.08
16.1
2.35
16.3
2.64
17.6
2.94
1800
15.5
2.20
16.3
2.45
17.0
2.76
17.7
3.05
1850
15.8
2.32
16.5
2.58
17.2
2.87
17.9
3.19
1900
16.0
2.46
16.7
2.70
17.5
2.99
18.1
3.31
BkW — Fan Input kW x Motor Efficiency
R/s
— Revolutions Per Second of Blower Wheel