beautypg.com

Wiring instructions, Control voltage wiring, Phase connections – Cadet CEH-005M User Manual

Page 4: Front back

background image

DUAL RATED 240/208 VOLT MODELS:

All 240 volt models may be operated at 208 volts with a corresponding
reduction in output.

3-Phase Connections

Single or 3-phase power connections may be used on 240/208 volt,
5 KW models. These units come factory wired for single-phase
power but may be wired for 3-phase power by reconnecting two
wires. This is done as follows:

Models with Line Voltage Control (See Figures 10 and 11)
a. Disconnect the orange wire from the junction block terminal and

connect it to the orange wire on the small terminal block and,

b. Disconnect the red wire from the junction block and connect it to

the terminal in the center of the block.

CAUTION – READ THESE INSTRUCTIONS CAREFULLY WHEN USING ALUMINUM WIRING

1. Carefully strip insulation from aluminum conductors and coat ends of conductors with suitable corrosion inhibitor (“Pentrox A”

or equivalent).

2. Wire brush aluminum surface, removing corrosion; re-coat with corrosion inhibitor.
3. Connect aluminum wiring and tighten connection securely. CAUTION: Do not exceed pressure needed for making a typical copper

connection.

4. Coat entire connection with inhibitor.
5. All connections using aluminum conductors should be periodically re-checked for tightness.
6. NOTE: DO NOT JOIN ALUMINUM CONDUCTORS DIRECTLY TO COPPER.

H

1

H

2

P

1

P

2

F

2

F

1

This model comes factory wired for single phase. When this
model is converted in the field to 3-phase, control hookup
should be provided by a CEK-TB2 (built-in thermostat). A 2-stage
or modulating wall thermostat can be used if hooked up correctly
and according to wiring diagram.

4. Connect the thermostat wires to terminals H1 and P1 as shown in

Figure 12. On 208 and 240 volt, single-phase model with line
voltage control, install jumpers as shown in Figure 12.

1. A knockout is also provided in the back of the unit for control

wiring. This knockout is sized for 1/2” conduit. (See Figure 12)

2. Thermostat wire shall be as follows:

a. Line voltage control: Use NEC Class 1, 600V, 90˚C, AWG #10
wire with copper conductor or same gauge wire as supply line.

3. Install wall thermostats in accordance with the installation

instructions supplied with the thermostat.
NOTE: Do not locate thermostat in an area exposed to unusual
temperature conditions or poor air circulation.
NOTE: Line voltage control model of 5KW rating that is 208 and
240 volt, wired for 3-phase operation, should not be used with
a wall thermostat.

Control Voltage Wiring

Figure 12

Thermostat wiring connections
---- Denotes optional equipment

Figure 13

Manual reset limit

Two manual reset thermal limits
are factory installed on all models.
The limits are located on the front
of the heater. The manual reset limits
will not reset until the buttons are
pushed and heater has cooled down.

FRONT

BACK

FRONT

Line Voltage
Control Models
(Singe Phase):

Install jumpers
between H

1

and H

2

and P

1

and P

2

on

208/240V units
(note dashed lines)

Manual Reset Limits

Heater Elements

Control Terminal Board

Connect Thermostat

Wires To P

1

and H

1

To Thermostat

Heater

elements

Orange

wire

Orange

wire

Junction block

for field wiring

Red

wire

Terminal

block

FRONT

BACK

Factory wired for

single phase

power (line

voltage control

models).

Wiring Instructions

NOTE: Supply wires must feed direct from breaker to junction block. Thermostat wires connect to terminal board. See wiring diagram.

Figure 10

Heater

elements

Orange

wire

Orange

wire

Junction block

for field wiring

Red

wire

Terminal

block

FRONT

BACK

Wired for

3-phase power

(line voltage

control models)

Figure 11

4