Vermont castings ewf36a, Finish wall, Mantels – Vermont Casting EWF36 User Manual
Page 15: Side wall protection
15
Vermont Castings EWF36A
20005167
Finish Wall
Finish the wall with material of your choice. Do not
install a combustible mantel shelf less than 12” (305
mm) above the firebox grille opening. Do not install
a mantel face plate less than 6” (159 mm) from top
of grille opening. (Fig. 20) If a combustible material is
used below a flat mantel shelf, consult your local build-
ing codes for minimum clearance from top of fireplace
opening to bottom of mantel shelf.
All joints (top, bottom and sides) where wall or deco-
rative facing material meets fireplace surround must
be completely sealed with a noncombustible material.
(Figs. 21 and 25)
NOTE: No side wall protection is required for fireplaces
installed at 45° to two (2) side walls (corner installation).
FP531
Fireplace surround detail
1/29/99 djt
Must be sealed with
noncombustible material
Mantel Shelf
Side View
Finished Wall
2 x 4 Stud
Standoff
Cast Front
See mantel drawing for
shelf-to-grille dimension
1” (25mm)
Fireplace
Front (Steel)
2 x 4 Stud
FP1200
Fig. 21 Finishing materials placement.
Brick Ledge
Noncombustible Finish Mate-
rial Only in this Area
Top View
Mantels
The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting heights and widths, refer to
Figures 22 and 23. When using paint or lacquer to finish
the mantel, such paint or lacquer must be heat resistant
to prevent discoloration.
FP1398
Fig. 22 Combustible mantel minimum opening.
FP1398
wood mantels
8/18/03 djt
6"
(159mm)
Min.
12"
(305mm)
Min.
1���"
(38mm)
12"
(305mm)
Max.
Combustiible
Mantel and
Trim
Finished Wall
Header
Standoff
Noncombustible
Material
Brick Ledge
GrilleOpening
Fireplace Front
MA81
Fig. 23 Combustible mantel clearances.
MA81
rev. 8/5/97
*
1���"
Ref.
**
Combustible materials
are permitted within a
shaded area shown in
Figure 26 titled
Minimum Wall
Clearances
* 12” (305mm) from top of grille opening.
** 6” from top of grille opening.
Side Wall Protection
Adjacent combustible side walls that are within mini-
mum dimensions shown in Figure 25 of the fireplace
opening must be protected with CFM Corporation Wall
Shield Model SP40 or a specifically built wall shield
described in Figure 20.
The special wall shield design described in Figure 20 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must =1.85
minimum.