Radiance direct vent/natural vent gas heater, Wall centerline from floor, Hearth requirements – Vermont Casting 3390 EN User Manual

Page 6: Wall and ceiling clearances

background image

6

6

Radiance Direct Vent/Natural Vent Gas Heater

20004188

Parallel Installation: Minimum Clearance

and Flue Centerline, Direct Vent and Natu-

ral Vent

Fig. 3 Parallel installation, minimum back and side clear-
ances, and flue centerlines.

ST130

�����
������������
�����

42" (1070mm)

Min. Alcove Width

48"

(1220mm)

Max. Alcove

Depth

6"

(150mm)

6"

(150mm)

4" (102mm)

ST129

�����
������������
�����

18"

(457mm)

18"

(457mm)

6"

(150mm)

6"

(150mm)

��

��

Corner Installation: Minimum Clearance and

Flue Centerline, Direct Vent & Natural Vent

Fig. 4 Corner installation, minimum corner clearances and
flue centerline.

Wall Centerline from Floor

ST131b

Stardance

wall thimble

9/28/00 djt

A

A

Effective Minimum
Centerline

57” (1448 mm)

(CFM Corporation Pipe)

55” (1399 mm) (Simpson DuraVent Pipe)

ST131b

Fig. 5 Minimum wall centerline.

Direct Vent Only

Hearth Requirements

The Radiance Heaters must be installed on rigid floor-
ing. When the heater is installed directly on any com-
bustible surface other than wood flooring, a metal or
wood panel extending the full width and depth of the
unit must be used as the hearth. There are no other
hearth requirements.

* needed for installing DuraVent Minimum Vent Kit #2792 or
CFM Corporation Minimum Vent Kit #7TFSMSK.

A

C

D

ST101b

Stardance

Direct Vent

Min. Clrnc

9/28/00 djt

B

A: Rear Wall

4” (102 mm)

B: Min. Clearance

44” (1118 mm)*

C: Min. Alcove Height

72” (1830 mm)*

D: Max. Alcove Depth

48” (1220 mm)

Sidewall Clearance

6” (150 mm)

ST101b

Fig. 6 Dimensions and clearances to ceiling or alcove.

Direct Vent Only

Wall and Ceiling Clearances