beautypg.com

Physical description, Industry compliance, Important notes – Crestron electronic iLux CLS-C6RF User Manual

Page 2: Installation, Ilux, Integrated lighting systems w/infinet

background image

iLux

Integrated Lighting Systems w/infiNET

Important Notes

CLS-C6RF & CLS-C6MRF Specifications (Continued)

SPECIFICATION

DETAILS

Environmental Temperature

32° to 104°F (0° to 40°C)

Humidity

10% to 90% RH
(non-condensing)

Overall Dimensions:
Height
Width
Depth


4.48 in (11.38 cm)
8.89 in (22.58 cm)
2.47 in (6.25 cm) for CLS-C6
2.60 in (6.61 cm) for CLS-C6M

Weight

22.8 oz (646.37 g)

Read before installation.

Codes: Install in accordance with all local and

national electrical codes.

Wiring: Use copper wire only. For supply

connections, use wires rated for at least 75°C.

Lighting Load Types: incandescent, magnetic

low voltage, neon/cold cathode, dimmable
2-wire fluorescent, and non-dim lighting
(also: electronic low voltage, 3-wire and 4-wire
fluorescent, and 277V via expansion modules; sold
separately).

1. Additional load types can be controlled and load ratings can be increased via

optional CLS-EXP expansion modules. Refer to the Crestron website

http://www.crestron.com/

for details.

Temperature: The iLux units are designed for use

where temperatures are between 32° to 104°F
(0° to 40°C).

2. The latest software versions can be obtained from the Crestron website. Refer to

the NOTE following these footnotes.

3. Crestron 2-Series control systems include the AV2 and PRO2. Consult the latest

Crestron Product Catalog for a complete list of 2-Series control systems.

Wallboxes: The iLux units mount in standard

4-gang wallboxes; 3.5 inches deep, minimum.

NOTE: Crestron software and any files on the website are
for Authorized Crestron dealers and Crestron Authorized
Independent Programmers (CAIP) only. New users may be
required to register to obtain access to certain areas of the
site (including the FTP site)

Make certain that power is turned off, and

ensure that there is at least 4.5 inches of open
space above and below the electrical box location
to permit heat dissipation.

Physical Description

Installation

The following illustration shows the overall dimensions for
the CLS-C6RF and CLS-C6MRF.

WARNING: Turn off power at the distribution panel
circuit breaker. Installing with power on can result in
serious personal injury and damage to the device.

CLS-C6MRF Overall Dimensions

CAUTION: To reduce the risk of overheating and possible
damage to other equipment, do not install to control a
receptacle or a motor-operated appliance.

NOTE: The CLS-C6RF units require a neutral wire for
operation. If no neutral is present, contact a licensed
electrician for installation.

The following tools/hardware are required for installation.

• A 4-gang electrical box (not supplied), 3.5 inches

deep, minimum.

• Phillips torque screwdriver (not supplied)

Industry Compliance

• Four 7/8-inch pan head Phillips screws (supplied)

This product is Listed to applicable UL Standards and
requirements by Underwriters Laboratories Inc.

If the planned configuration includes connection to shade
controllers, keypads, and/or a Crestron 2-Series control
system, the following items are also required. Refer to the
latest version of the Crestron CLS-C6RF iLux Integrated
Lighting System w/infiNET Operations Guide (Doc. 6418)
for detailed configuration options.

(E103692)

NOTE: This device complies with part 15 of the FCC
rules. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and (2)
this device must accept any interference received, including
interference that may cause undesired operation.

• Cresnet network cable(s) (not supplied)
• Terminal block connector(s) (two supplied)

2

iLux

Integrated Lighting Systems w/infiNET

: CLS-C6RF & CLS-C6MRF

Installation Guide – DOC. 6416A

This manual is related to the following products: