beautypg.com

F-16 controls – Dynalco F-16 Frequency Generator/Counter User Manual

Page 2

background image

Azonix-Dynalco, 3690 N.W. 53 Street, Fort Lauderdale, FL 3330 U.S.A.

(954) 739-4300 • Fax (954) 484-3376 • www.dynalco.com • [email protected]

F-16 CONTROLS

CALIBRATION EXAMPLE

Determine setpoint value on an SW-50 Series Speed Switch — on the bench

J

Turn on the F-16.

J

Set the F-16 to a low frequency—below what would be expected to trip that
setpoint.

J

Attach the red F-16 lead to Terminal 3 on the SW-50.

J

Attach the black F-16 lead to terminal 2 on the SW-50.

J

Make sure the F-16 is set to GENERATOR.

J

Slowly increase the frequency on the F-16.

J

Using an ohmmeter across each relay contact, in turn, determine the frequency
at which the relays change state.

Note: An overspeed relay will latch if terminal 4 is not grounded.

Change setpoint value on an SW-50 Series Speed Switch — on the bench
Remove the screws in the access holes for the required setpoint adjustment trim pots.

J

Set the signal generator to the frequency at which the relay should change
state.

J

Using a small, flat blade screwdriver, slowly adjust the trim pot for the
appropriate relay until the relay changes state.
• CW to increase the setpoint value
• CCW to decrease the setpoint value

J

Decrease the frequency, then slowly increase it to verify that the relay trips at
the appropriate point.