Majestic, Fireplaces power venting system, Installation restrictions – CFM Corporation PVS-1 User Manual

Page 5: Installation

background image

5

Majestic

®

Fireplaces Power Venting System

51810

FP1417

powervent

system

front view

11/24/03 djt

4” (102 mm) Insu-

lated Flue Liner

Sound Reducer

Sheet Metal

Screws

Fireplace Top

Fireplace

FP1417

Fig. 1 Secure sound reducer to fireplace top with four (4)
sheet metal screws.

Installation Restrictions

Sound Reducer Kit SR6
1. Although the Power Venter can be installed any-

where in the exhaust system, it is best if it is installed
as close to the termination of the vent system as
possible to obtain optimal appliance efficiency and to
prevent flue gas leakage. (Fig. 2)

FP1418

power vent location

11/24/03 djt

Vent Support Hangers

Spaced 36” (914mm) on

Horizontal Run

Anti-Vibration Sleeve

FP1418

Fig. 2 It is best to install Power Venter as close to the termi-
nation as possible.

2. Power Venter must be mounted with motor shaft hor-

izontal to ensure proper operation of the fan proving
switch and to prevent motor bearing wear. (Fig. 3)

FP1419

motor views

11/25/03 djt

Horizontal Discharge

Vertical Discharge

Oil Holes

Motor Shaft

Vertical

Incorrect

FP1419

Fig. 3 The Power Venter must be mounted with motor shaft
horizontal.

3. Power Venter housing in single wall a 6” (152 mm)

clearance must be maintained. (Fig. 4)

6" (152mm)

Minimum

6" (152mm) Minimum

6" (152mm) Minimum

FP1420

Minimum clearance

11/25/03 djt

Combustible Material

Combustible Material

Combustible Material

Power Venter

NOTE: 6” (152mm)

maximum clearance from

combustible must be

maintained.

FP1420

Fig. 4 Minimum clearance.

4. Allow for a minimum of 18” (457mm) vertical rise off

the top of the appliance before the vent makes a 90°
elbow to the horizontal. (Fig. 5)

5. Vent pipe transitions, where necessary, should be

gradually tapered. (Fig. 6)

6. Power Venter to vent pipe connections and all joints

on the outlet side of the Power Venter must be
sealed with high temperature silicone sealant or alu-
minum vent pipe tape to prevent flue gas leakage.
(Fig. 7)

7. The vent terminal must not be more than 20’ (6m)

below the appliance’s flue outlet.

Installation

1. Slip Sound Reducer into flue collar and press on to

fireplace top.

2. Fasten Sound Reducer to fireplace top with four (4)

sheet metal screws supplied.

3. Continue with the power venter installation as per

instructions supplied with same.