DEFINITIONS FOR LED INDICATORS

Power

On

Wiring

Fault

AVR

Using

Battery

Circuit

Breaker

Alarm

Condition

On Off Off Off Set Off

Normal

On Off Flash Off Set Off

AVR- Max. boost 15% of input
voltage for output regulation
while input voltage is from 8% to
30% under nominal.

ON Off On Off Set Off

AVR- Max. buck 15% of input
voltage for output regulation
while input voltage is from 8% to
26% over nominal.

Off On/Off Off On Set

Two

Beeps

Utility Failure- The UPS is
providing battery power to the
Battery-Power Supplied outlets.

Off On/Off Off On Set

Rapid

Beeps

Utility Failure- The UPS is
providing battery power.
Rapid beeps indicate the
battery will run out of charge
within a few minutes.

On/Off On/Off

On/ Off

/Flash

On/Off

Set

Long

Beep

Overload- Turn the UPS off
and unplug at least one piece of
equipment from the UPS. Wait
5 seconds, reset the circuit
breaker and restart the UPS.

Off Off Off On Up

Long

Beep

Overload- Turn the UPS off
and unplug at least one piece of
equipment from the UPS. Wait
5 seconds, reset the circuit
breaker and restart the UPS.

On On/Off

On/ Off

/Flash

Off Set

None

Weak Battery- Recharge the
battery for at least 8 hours. If
Check Battery is illuminated,
contact CyberPower Systems
for battery replacement
information.

Off Off Off Off Set Off

Surge Protection
Malfunction-
Power surge has
damaged the unit. Please
contact CyberPower Systems

On/Off On

On/ Off

/Flash

On/Off

Set/Up

None

Electrical Wiring Fault-
Indicates wiring problems such
as a bad ground, missed
ground or reversed wiring
within the AC outlet. User is
advised to disconnect all
electrical equipment from the
outlet and have the outlet
checked by an electrician.

8