8
Malfunctions
Clogged strainer basket
Remove and dismantle entire strainer basket, 
clean or replace and install again. 
See Section 9.1 and 9.2.
Strainer basket sticks
If functional parts swell owing to the medium, it is 
very difficult to remove the strainer basket. 
If dismantling is not possible by pulling the unit 
upwards, remove cover 106 and push the strainer 
basket upwards from below. 
Dismantling by pushing downwards is not possible 
owing to the anti-torsion insert 219.
Flange connection ball valve/pipe is leaking
Retighten the flange screws to a tightening torque 
according to Section 1.2. If this does not remedy 
the leak, the recommended torques may be 
exceeded by 10%. 
If this also fails to stop the leak, dismantle and 
inspect the valve. 
 
9
Maintenance
All repair work is to be performed by qualified 
personnel using the appropriate tools. 
For the arrangement, designation and item 
numbers of all parts of the valve, see Section 10.
Spare parts are to be ordered with all the details in 
acc. with the valve identification. 
Only original spare parts may be installed.
Make sure that the strainer is empty when 
work is performed on it. 
To prevent leaks, a regular check of the connection 
screws should be made in line with the operating 
requirements. 
For tightening torques, see Section 1.2.
9.1 Dismantling of the strainer
basket
Observe shutdown procedure in Section 7.3.
Undo cover fittings 902/1, 936/1 and 920/1 and 
remove upper cover 107 and cover disc 115.
Screw ring bolt 900/1 into the strainer basket 220 
and pull the strainer basket with the seal ring 407 
up and out. 
If the strainer basket is cleaned or replaced when 
the valve is installed, attention must be paid when 
opening to residual medium in the plant. 
Observe safety regulations when handling 
the medium. 
Mark position of the inner and outer tubes in 
relation to the round cord 522 
Pull round cord 512 out of the strainer basket 
bottom 218.
Pull out outer tube 234.
The filter web 216 or the entire strainer basket 220 
can now be cleaned or replaced. 
For cleaning purposes, only use soft and/or liquid 
cleaning materials. 
9.2 Installation of the strainer
basket
Insert seal ring 407 into the inner tube 222.
Place the filter web 216 (new or cleaned) with an 
overlap over the inner tube 222.
Place the outer tube 234 over the inner tube with a 
rotary movement. Do not turn against the overlap! 
Insert the inner and outer tubes together into the 
strainer basket bottom 218.
Insert the round cord 522 again in accordance with 
the markings. 
Insert the complete strainer basket into the strainer 
basket support 217. Pay attention to anti-torsion 
insert 219.
Screw the upper cover 107 and cover disc 115 
tight with the stud screw 902/1, a toothed lock 
washer 936/2 and hex. nut 920/1.
For tightening torques, see Section 1.2.
9.3 Option Draining
Instead of the cover 106 a transition cover 109 is used 
with this option. 
A valve (DN 15 as standard or other DN on request) 
can be connected to it. 
See sectional drawing in Section 10.3.