Klimaire 13 SEER Series User Manual
Page 13
12
1/2
” bolt
5/16
” bolts
Fig. 9 COVER AND FAN
3.10 REMOVING THE TOP PANEL AND MOTOR
When motor requires changing follow the steps below:
Step 1: Go into electrical panel, disconnect motor power lines.
IMPORTANT NOTE
Disconnect main power to unit. Severe burns and electrical shock will occure if
you do not disconnect main power.
Step 2: Remove cover (be careful of motor wires)
Step 3: Be sure to place fan cover unit on the ground as indicated in Fig. 9
IMPROTANT NOTE
Do not place or lean fan blades on ground or against surface.
Step 4: Remove fan motor by removing 5/16
” bolts from cover.
Step 5: Remove fan blade from motor by removing 1/2
” bolt and place fan on the ground.
Step 6: Reverse removal process to reinstall the fan and motor.
IMPROTANT NOTE
When connecting motor wires be sure to check motor direction.
DESCRIPTION
1/4
” Χ 3/8” Hex Washer Head Concrete Screws
1/8
” Χ 1-1/2” Χ W (width of unit +4”) Metal straps
3/8
” Washers
QUANTITY
4
4
4
Step 4: Fasten (4) L-shaped stainless steel braces onto cabinet base using 1/4
” * 1/2”
Hex washer head stainless steel self tapping screws where indicated in detail
Fig.8.
IMPORTANT
Do not use screws longer than indicated 1/4
” * 2/3” and make sure that the brace
is attached on center of base ban where indicated in Fig.8
Damage will occrue to system.
Step 5: Drill 4 holes into cement base ensuring holes are 1//2
” dp.
Step 6: Assemble unit to cement pad using 1/4
” * 2” Hex washer head cement
screws make sure not to over tighten.
Step 7
:Finish unit assembly process as indicated in installation manual.
Step 1: Prior to installing clear pad of debris.
Step 2: Ensure cement pad is level.
IMPORTANT
Then cement pad must be made of HVAC-approved materials and must be the
proper thickness to accommodate fasteners.
Step 3: Center unit onto pad.
Damage will occur to condenser unit
if you remove fan bolts prior to cover removal.
NOTE: