HMX Specifications
Communications Bus: The communications bus conforms to the RS-485 standard and requires the use of
UTP- cable for 1M Baud data rates. Wiring must be run in conduit in a daisy chain from the Master Panel to
the first Dist. Panel, from each Dist. Panel to the next Dist. Panel and from the last Dist. Panel back to the
Master Panel. When style 7 wiring is used, a separate conduit for each bus must be used.
Voltage: 5V peak-to-peak max.
Current: 50mA max.
Impedance: 120 Ohms
(max. imp. between panels)
Frequency: 1.024MHz
Power Requirements: Power supplied to the DCC module is routed to any attached peripherals. These
peripherals in turn determine whether the DCC is part of a Master Panel or a Dist. Panel.. Amplifier modules
in Dist. Panel are powered separately.
Battery Charging
Maximum charging current from EVX-25/50 is 800mA.
Maximum battery size* is 18Ah for EVX-25E and EVX-50E.
Maximum Battery size* for EVX-100E is 24 Ah.
* 12 amp hour is maximum size that will house in a MP or DP cabinet
Electrical Ratings
All circuits @ 24 VDC
MASTER PANEL
Stand by condition
Alarm condition
DCC
73mA
*147mA combine DCC, ASC & MMC
ASC
34mA
MMC
38mA
MFP
10mA
20mA
MFH
12mA
12mA
IOI
19mA
30mA
SSC
29mA
15mA
SLC
0.2mA
8mA
TOTAL
215.2
232mA
DISTRIBUTED PANEL
Stand by condition
Alarm condition
DCC
76mA
*104mA combine both DCC and MBR
MBR
28mA
AMI
16mA
26mA
FPI
20mA
41mA
MBK
6mA
42mA
TOTAL
149mA
213mA
P/N HS-5010 REV. C
page 12 of 12