—5—

The BW9, unlike normal residential atmospheric and induced draft
boilers, takes its combustion air directly from the outdoors (sealed
combustion) and does not compete with building occupants for
fresh air. Sealed combustion (also known as “direct vent”) is the
safest and best way to obtain plenty of clean combustion air. The
induced draft fan draws in the outside combustion air, then takes the
cooler flue gases from the heat exchanger and provides a positive
removal of the flue gases from the building through inexpensive and
readily available PVC and CPVC pipes.

FEATURES

RANGE OF CAPACITIES

—Three sizes ranging from 50,000

through 100,000 Btuh input.

COMPLETELY PACKAGED

—Each boiler is completely

assembled, including all controls (except room thermostat). All
necessary wiring is factory installed. The boiler is ready for gas
piping, room thermostat, and electrical power connections as
shipped. Circulator is shipped pre-wired with 6 ft bx conduit for
easy installation for supply side pumping.

VENTING

—This boiler is direct vented with PVC and CPVC pipe.

See the Installation Instructions for common venting requirements.

ALUMINUM SECTIONS

—These sections speed heat transfer to

the boiler water. With faster thermal response, greater comfort and
economy are achieved.

PRE-MIX BURNER

—Provides quiet operation and improved

combustion efficiency.

CONTROLS

—Integrated Boiler Control provides safe,

dependable operation of burners. Factory-installed safety
components provide maximum safety against overheating,
pressure buildup, and low-water operation.

SECTIONS TESTED

—Each section is hydrostatically tested to

50 psig. Individual sections are tested to 125 psig at factory.
Assembled sections are tested to 75 psig at the factory. The
maximum allowable pressure is 50 psig for hot water boilers.

PROPANE CONVERTIBLE

—With factory approved conversion

kit accessory.

WARRANTY

—The aluminum sections are covered by a limited

15-year warranty on the entire assembly. Circulator pump is
covered by a limited 3-year warranty. All other parts are covered
by a 1-year limited warranty.

SPECIFICATIONS

UNIT SIZE

050

075

100

Sections

1

GAS CONTROLS

Gas Valve

Honeywell

Inlet Size

In.

1/2

Ignition

Hot Surface Ignition

Burner—Stainless/Titanium Alloy

1

Burner Orifice

No.

0.0615

#48

#44

CONTROLS

Limit Control Range

°F

100-200

Pressure Relief Valve Setting

Psig

30

Integrated Boiler Control

UTEC factory installed

CIRCULATOR

Taco

Model

007

Full Load Amps

2.0 AMPS/330 WATTS

Flange Size FPT

In.

1-1/4

The BW9 is a gas fired direct vent condensing hot water
boiler with cast aluminum heat exchanger sections. A
revolutionary cast aluminum heat exchanger means better
heat transfer and thermal storage than similarly sized cast
iron boiler, which results in higher efficiency. The heating
system water absorbs large amounts of heat from the cast
aluminum heat exchanger, cooling the flue gases and
causing condensation. Sealed combustion, premix gas
burner, and low flame temperature means drastically
reduced CO and NOx emissions, which contribute to a
cleaner and healthier environment.