The following terms are used throughout this manual to bring attention to the presence of hazards of various risk
levels.

WARNING

Indicates a potentially hazardous situation which,

if not avoided, could result in death, serious injury

or substantial property damage.

CAUTION

Indicates a potentially hazardous situation which,

if not avoided, may result in moderate or minor

injury or property damage.

Basic Operation

A.

General. This water boiler is equipped with controls

for proper operation. All controls must be in proper

working order. Contact a qualified service agency to

provide annual maintenance as specified in Installation,

Operating and Service Instructions.
1. Limit.

See Figure 1. A device which automatically

interrupts boiler operation when the water
temperature exceeds the set point. Maximum
allowable temperature is 220°F.

Original equipment with this boiler is U.S. Boiler

IQ Control and Limit Rated Sensor combination.

The IQ Control shuts off boiler main burners when
boiler water temperature exceeds pre-programmed

IQ control water temperature set point. Boiler main

burners will re-light automatically, providing the call

for heat is present, when boiler water temperature
falls below pre-programmed control water
temperature set point less the set point differential.

2. Flame Rollout Switch.

See Figure 1. A device

which automatically interrupts boiler operation

when flames or excessive heat are present in the
combustion area enclosure. The control is a single

use device. The control is located in the combustion

area enclosure. If the control was activated to

interrupt boiler operation, do not attempt to place

boiler in operation. Contact a qualified service

agency.

WARNING

Service on this boiler should be undertaken only

by trained and skilled personnel from a qualified

service agency.

WARNING

Do not reset Blocked Vent Switch unless a

qualified service agency has determined and

corrected the cause of any blockage in the vent

system or chimney.

3. Blocked Vent Switch

See Figure 1. A device

which automatically interrupts boiler operation

when excessive vent system blockage occurs. If the

control was activated to interrupt boiler operation,
do not attempt to place boiler in operation. Contact

a qualified service agency.

4. Electronic Ignition System - see Figure 1. The

Electronic Ignition (EI) System consists of:
a. a solid state ignition control with integral

ignition module to initiate, monitor and stop
burner operation.

b. a combination gas valve to regulate gas flow to

the main burners.

c. a pilot burner to provide the ignition source for

the main burners.

B.

Instructions to place the boiler in operation and to turn

off the boiler are shown on the Operating Instruction

Label posted on the left jacket panel of the boiler. The

Operating Instruction Label is shown in Figure 2.

C.

The Sequence of Operation is shown in Figure 3.

CAUTION

Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical

supply to the pump. Instead, shut off the gas supply at a location external to the appliance.

En cas de surchauffe ou si I'admission de gaz ne peut étre coupée, ne pas couper ni débrancher

l'alimentation électrique de la pompe. Fermer plutôt le robinet d'admission de gaz à l'extérieur de I'appareil.
Do not use this boiler if any part has been under water. Immediately call a qualified service technician to

inspect the boiler and to replace any part of the control system and any gas control which has been under

water.