Calculated Industries 5070-A Pocket Reference Guide User Manual
Page 27

P
ocket
R
efeRence
G
uide
— 27
(cont’d)
3. Set to Copper (if necessary):
(Cu/Al)
1 Ø 75 Cu
1 Ph
4. Enter Amps:
AMPS 11.
5. Enter Volts:
VOLT 208.
6. Enter Length:
FEET 175.
7. Enter Wire Size:
AWG 8 Cu
WIRE SIZE
8. Solve Voltage Drop:
DROP 3.0
V
9. Solve percent Voltage Drop:
DROP 1.4
%
V
Finding Voltage Drop Wire Size
A 20 Amp, 3Ø 208 Volt load will be
located 175 Feet away from the source.
Assuming a 3% allowable Voltage Drop,
what is the size of 75°C conductor
required for this branch circuit?
KEYSTROKE
DISPLAY
0.
1. Set to 3-Phase:
(3Ш)
3Ш Ph
2. Set to 75º C:
(75º C)
3Ø
75
3 Ph
KEYSTROKE
DISPLAY
See also other documents in the category Calculated Industries Calculators, organizers:
- 4215 (64 pages)
- 4225-B (52 pages)
- 4225-C (52 pages)
- 44060 (134 pages)
- 4050 Metric Edition (44 pages)
- 4050 (52 pages)
- 4050 v3.1 (52 pages)
- 4050-F (52 pages)
- 4054 (52 pages)
- 4045-B (54 pages)
- 4045 (26 pages)
- 4067 Pocket Reference Guide (52 pages)
- 4067 User Guide (23 pages)
- 4065 v3.0 (108 pages)
- 4065 v3.1 Pocket Reference Guide Construction Master Pro (39 pages)
- 4065 v3.1 Pocket Reference Guide Advanced Consnruction-Math (40 pages)
- 4065 v3.1 User Guide (110 pages)
- 8030 (44 pages)
- 5025 (48 pages)
- 5065 (71 pages)
- 5070-B Pocket Reference Guide (46 pages)
- 5070-A User Guide (66 pages)
- 5070-B User Guide (66 pages)
- 4315 (56 pages)
- 4320 (51 pages)
- 4325 (53 pages)
- 4090 (123 pages)
- 4019 (40 pages)
- 4018 (38 pages)
- 4015 (84 pages)
- 4020 (39 pages)
- 4095-A Pocket Reference Guide (36 pages)
- 4095-B Pocket Reference Guide (38 pages)
- 4095-C Pocket Reference Guide (23 pages)
- 4095-A User Guide (50 pages)
- 4095-B User Guide (68 pages)
- 4095-C User Guide (65 pages)
- 4094 Pocket Reference Guide (38 pages)
- 4094 User Guide (44 pages)
- 8545 (48 pages)
- 4400 (50 pages)
- 8015 (64 pages)
- 8020 (52 pages)
- 8025 (47 pages)