Bryant 549B User Manual
Page 115
115
PERFORMANCE DATA — 549B, 549C (cont)
FAN RPM AT MOTOR PULLEY SETTINGS*
*Approximate fan rpm shown.
†Indicates standard motor and drive package.
**Indicates high-static motor and drive package.
INDOOR-FAN MOTOR PERFORMANCE — STANDARD MOTORS
INDOOR-FAN MOTOR PERFORMANCE — HIGH-STATIC MOTORS
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors
can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
UNIT
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
549C024
936
906
877
847
817
788
758
728
698
669
639
—
—
549B, 549C036†
1044
1008
971
935
898
862
826
789
753
716
680
—
—
549B036**
1455
1423
1392
1360
1328
1297
1265
1233
1202
1170
1138
1107
1075
549B, 549C048†
1185
1144
1102
1061
1019
978
936
895
853
812
770
—
—
549B048**
1455
1423
1392
1360
1328
1297
1265
1233
1202
1170
1138
1107
1075
549B, 549C060†
1460
1425
1390
1355
1319
1284
1249
1214
1179
1144
1108
1073
1038
549B060**
1685
1647
1608
1570
1531
1493
1454
1416
1377
1339
1300
—
—
549B072†
1585
1538
1492
1445
1399
1352
1305
1259
1212
1166
1119
—
—
549B072**
1685
1647
1608
1570
1531
1493
1454
1416
1377
1339
1300
—
—
549B090†
950
930
905
885
865
840
820
795
775
750
730
—
—
549B090**
1080
1060
1035
1015
990
970
950
925
905
880
860
—
—
549B102†
1085
1061
1036
1012
987
963
938
914
889
865
840
—
—
549B102**
1080
1058
1036
1014
992
970
948
926
904
882
860
—
—
549B120†
1080
1060
1035
1015
990
970
950
925
905
880
860
—
—
549B120**
1219
1195
1170
1145
1120
1095
1071
1046
1021
996
972
947
922
UNIT
549B, 549C
UNIT
VOLTAGE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
MAXIMUM
AMP DRAW
MOTOR
EFFICIENCY
024
ALL
0.58
580
2.0
75.0
036
208/230-1-60
1.20
1195
4.9
75.0
208/230-3-60
1.20
1195
4.9
75.0
460-3-60
2.3
75.0
048
208/230-1-60
1.20
1195
4.9
75.0
208/230-3-60
1.20
1195
4.9
75.0
460-3-60
2.3
75.0
060
208/230-1-60
1.30
1290
7.6
74.0
208/230-3-60
2.40
2120
6.0
84.0
460-3-60
3.0
84.0
072
208/230-3-60
2.40
2120
6.0
84.0
460-3-60
3.0
84.0
090,
102
208/230-3-60
2.90
2615
8.6
80.0
460-3-60
2.90
2615
3.9
80.0
120
208/230-3-60
3.70
3313
11.7
85.0
460-3-60
3.70
3313
5.5
85.0
UNIT
549B,549C
UNIT
VOLTAGE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
MAXIMUM
AMP DRAW
MOTOR
EFFICIENCY
036
208/230-3-60
2.40
2120
6.0
75
460-3-60
3.0
75
048
208/230-3-60
2.40
2120
6.0
75
460-3-60
3.0
75
060
208/230-3-60
2.90
2615
8.6
84
460-3-60
3.9
84
072
208/230-3-60
2.90
2615
8.6
84
460-3-60
3.9
84
090,
102
208/230-3-60
3.70
3313
11.7
80
460-3-60
5.5
80
120
208/230-3-60
5.25
4400
17.3
85
460-3-60
8.5
85
549
B, 5
49C