Bryant T1--NAC User Manual

Page 3

background image

3

Available Selection:
Use UP and DOWN buttons to change between H and C.

Option 13 — Room Temperature Offset Adjustment

This option allows calibration (or deliberate miscalibration) of the
room temperature sensor. There are various reasons why

homeowners may want to have displayed temperature adjusted to a

higher or lower value. The selected number is the number of
degrees, plus or minus, which will be added to actual temperature.
The numbers can range between --5 and +5. Factory default is 0.
Available Selection:
Use UP and DOWN buttons to now move between --5 and +5 in
increments of 1.

Step 4 — Thermostat Operation

Temperature Display
Thermostat will display room temperature until UP or DOWN

button is pressed. The word SET appears when these buttons are

pressed and the current setpoint is displayed. If no buttons are
pressed for 5 sec, the display will change back to show room

temperature.
Timeguard Timer
A 5--minute timeguard is built into the thermostat immediately
upon power up, and any time the compressor turns off. The

compressor will not turn on until the timeguard has expired. The
timeguard affects only compressor operation. Pressing UP and

FAN buttons simultaneously will override the timeguard for 1

cycle. With PH or PC selected under Option 01, this timer is
defeated.
Cycle Timer
In normal heating and cooling operation the thermostat will not

allow more than 4 equipment cycles per hour (or 1 cycle every 15
minutes). Both the Y and W outputs have a 15--minute timer that

starts counting down when the output is turned on, (e.g., if Y
output is turned on for 9 minutes and then satisfies, it cannot turn

back on for another 6 minutes regardless of demand). However,

pressing UP and FAN buttons simultaneously or changing the
setpoint will override the timer for 1 cycle.
Minimum on Timer
Once the equipment has turned on, it will remain on for a

minimum of 3 minutes regardless of demand. However, the
equipment can turn off in less than 3 minutes if a change in

setpoint or a change in mode occurs.

Staging Timer
If the thermostat is a heat pump model, it has 2--stage heat

capability. With HP operation, there is a 15--minute delay between
the first and second stages of heat. The Y output will energize first,

then 15 minutes later, W is allowed to come on if the thermostat
determines it is not satisfying the demand.
However, if the heating demand is greater than 5_F, there will be

only a 30 second delay before bringing on W.
Auxiliary Heat Indicator
A green LED indicates the use of auxiliary heat or emergency heat.
Error Messages
“----” (two dashes) will be displayed if the thermostat cannot

properly read room temperature. If “----” appears, replace

thermostat.
E4 will be displayed if the thermostat has an internal memory

failure. If E4 appears, replace thermostat.

Step 5 — Check Thermostat Operation

Fan Operation

1. Press FAN button. This will start continuous fan operation.

FAN annunciator will turn on.

2. Press FAN button again. This will stop continuous fan

operation. FAN annunciator will turn off.

Heating Operation

1. Press H/C button until HEAT is displayed.
2. Press UP button until LCD readout reads 3_F above room

temperature. Press UP and FAN buttons simultaneously to
defeat timers. Heating system should begin to operate

immediately.

3. For HP thermostats only, press H/C button until EMHT

(emergency heat) appears. Press UP and FAN buttons

simultaneously to defeat timers. Emergency heating (W is
ON, Y is OFF) should begin immediately.

Cooling Operation

1. Press H/C button until COOL is displayed.
2. Press DOWN button until LCD readout reads 3_F below

room

temperature.

Press

UP

and

FAN

buttons

simultaneously to defeat timers. Cooling system should

begin to operate immediately.

Table 1 shows the thermostat outputs for each available stage of

heating or cooling. It may be useful in checkout or
troubleshooting.

Table 1 – Outputs

EQUIPMENT

CONFIGURATION

OPTION #1

THERMOSTAT

FACTORY

CONFIGURATION

COOL

STAGE 1

HEAT

STAGE 1

HEAT

STAGE 2

EM HEAT

AC, PC

AC, HP

Y, G

W

--- ---

--- ---

HP, PH

RVS = C

HP

Y, G, O/B

Y, G

Y, G, W

W

HP, PH

RVS = H

HP

Y, G

Y, G, O/B

Y, G, W, O/B

W

T1

--

NAC

/T1

--

NH

P