Bendix Commercial Vehicle Systems BA-921 COMPRESSOR_STD/CLOSED ROOM User Manual
Page 8

8
buildup indicates inadequate cooling. Closely inspect the 
compressor cooling system. Check all compressor coolant 
lines for kinks and restrictions to fl ow. Minimum coolant line 
size is 3/8" I.D. Check coolant lines for internal clogging 
from rust scale. If coolant lines appear suspicious, check 
the coolant fl ow and compare to the tabulated technical 
data present in the back of this manual. Carefully inspect 
the air induction system for restrictions.
LUBRICATION
Caterpillar Engine Installations.
Check the external oil supply line for kinks, bends, or 
restrictions to fl ow. Supply lines must be a minimum of 
3/16” I.D. Refer to the tabulated technical data in the back 
of this manual for oil pressure minimum values. 
Check the exterior of the compressor for the presence of 
oil seepage and refer to the TROUBLESHOOTING section 
for appropriate tests and corrective action. 
Detroit Diesel S60 Installations
On Detroit Diesel Series 60 engine installations, the 
compressor utilizes an internal oil feed design. Check 
the exterior of the compressor for the presence of oil 
seepage and refer to the TROUBLESHOOTING section 
for appropriate tests and corrective action. Refer to the 
tabulated technical data in the back of this manual for oil 
pressure minimum values. 
OIL PASSING
All reciprocating compressors pass a minimal amount of 
oil. Air dyers will remove the majority of oil before it can 
enter the air brake system. For particularly oil sensitive 
systems, the Bendix
®
PuraGuard
®
system can be use in
conjunction with a Bendix
®
air dryer.
If compressor oil passing is suspected, refer to the 
TROUBLESHOOTING section (starting on page A-1) 
for the symptoms and corrective action to be taken. In 
addition, Bendix has developed the “Bendix Air System 
Inspection Cup” or BASIC
™
kit to help substantiate
suspected excessive oil passing. The steps to be followed 
when using the BASIC
™
kit are presented in APPENDIX
B, on page A-16.
COMPRESSOR DRIVE
Check for noisy compressor operation, which could indicate 
excessive drive component wear. Adjust and/or replace 
as necessary. Check all compressor mounting bolts and 
retighten evenly if necessary. Check for leakage and 
proper unloader mechanism operation. Repair or replace 
parts as necessary.
COMPRESSOR UNLOADER & GOVERNOR
Test and inspect the compressor and governor unloader 
system for proper operation and pressure setting.
1. Check for leakage at the unloader port. Replace leaking
or worn o-rings.
2. Make certain the unloader system lines are connected
as illustrated in Figure 6.
3. Cycle the compressor through the loaded and unloaded
cycle several times. Make certain that the governor 
cuts-in (compressor resumes compressing air) at a 
minimum of 105 psi (cut-out should be approximately 
15 - 20 psi greater than cut-in pressure). Adjust or 
replace the governor as required.
4. Note that the compressor cycles to the loaded and
unloaded conditions promptly. If prompt action is not 
noted, repair or replace the governor and/or repair the 
compressor unloader.
IMPORTANT NOTE
Replacement air governors must have a minimum cut-in 
pressure of 100 psi. The cut-in pressure is the lowest 
system pressure registered in the gauges before the 
compressor resumes compressing air.
Compressors with no signal line to the unloader port should 
have a vent cap (e.g. Bendix part number 222797) installed 
in the port. Under no circumstances should the port be 
plugged or left open.
SERVICE TESTS
GENERAL
The following compressor operating and leakage tests need 
not be performed on a regular basis. These tests should be 
performed when it is suspected that leakage is substantially 
affecting compressor buildup performance, or when it is 
suspected that the compressor is “cycling” between the 
loaded (pumping) and unloaded (non-pumping) modes 
due to unloader leakage.
