LETTER AFTER MODEL NUMBER FOR PUMP NEEDED: G=2699-3 Speed(230V) M=26-116
B=NRF36
CAUTION: For proper operation, water must be added as air is eliminated. The amount of water will be in proportion to
the amount of air eliminated.
SYSTEM READY
The complete system is now operational and ready for testing. Use the flow meter tool (Part 1-WFT40) which slips over
the inlet pipe inside the flow center. Read the actual flow rate being pumped through the flow center. By closing all the
loop valves but one pair, an actual flow rate can be read on the meter for each ground loop. This will indicate that all
loops are flowing properly. If any loop shows a significant reduction of flow an obstruction may be present in the loop.
Remove flow meter from the flow center canister and allow the pumps to run continuously for 24 hours. The flow center
will continue to eliminate any small air bubbles that remain in the system.