TROUBLESHOOTING GE X13-SERIES ECM2.3

MOTORS

CONT’D.

Model X13 Communication Diagnostics

The X13 motor is communicated through 24 VAC low voltage
(Thermostat Control Circuit Wiring).

1.

Start with unit wiring diagram to confirm proper connections

and voltage (see Figure 14).

2. Initiate a demand from the thermostat and check the voltage

between the common and the appropriate motor terminal (1-5).
("G" input is typically on terminal #1, but refer to wiring
diagram!)

a.If the low voltage communication is not present, check the

demand from the thermostat. Also check the output
terminal and wire(s) from the terminal strip or control
relay(s) to the motor.

b.If the motor has proper high voltage as identified above

(Motor not Running #1), and proper low voltage to a
programmed terminal, and is not operating, the motor is
failed, and will require replacement.

24VAC "R" Signal through

thermostat output.

24VAC Common

24VAC Common

24VAC "R" Signal through

thermostat output.