Schwank TruTemp IR Setback Thermostat User Manual
Page 4
TruTemp Manual
IM080326
RD: Aug 2006
RL: 3C
KH
6
. Insert cable through cable opening in
TruTemp back plate. Attach back plate to
electrical box.
8. Connect leads to 'R', 'W', and `C' terminals
on TruTemp control. See attached
wiring diagrams for details.
9. Set TEMPERATURE dial to the level
desired during occupied times.
10. Turn LIGHT LEVEL knob counter-
clockwise to stop. With lights on (as
would be during normal occupied times),
slowly adjust the LIGHT LEVEL knob
clockwise just to the point when the
LIGHT indicator comes on. To test, turn
off building lights. LIGHT indicator should
shut off. Allow for time delay.
11. If setback is not desired, move the
setback disable switch (down) to the
disable position.
2